F-23 Start Speed [Hz]

Range:

Function:

0 Hz

*

[0 -

500.0 Hz]

This parameter can be used for hoist

applications (cone rotor). Set a motor start

speed. After the start signal, the output speed

leaps to set value. Set the start function in

F-25 Start Function to [3] Start speed cw, [4]

Horizontal operation or [5] Adv. Vector Control/

Flux Clockwise, and set a start delay time in

F-24 Holding Time.

F-24 Holding Time

Range:

Function:

0 s

*

[0 - 25.5 s] This parameter refers to the start function

selected in F-25 Start Function.

Enter the time delay required before

commencing acceleration.

F-25 Start Function

Option:

Function:

Select the start function during start delay.

This parameter is linked to F-24 Holding Time.

[0]

DC Hold/

delay time

Energizes motor with a DC holding current

(B-00 DC Hold Current) during the start delay

time.

[1]

DC Brake/

delay time

Energizes motor with a DC braking current

(B-01 DC Brake Current) during the start delay

time.

[2]

*

Coast/delay

time

Motor coasted during the start delay time

(inverter off).

[3]

Start speed

cw

Only possible with Advanced Vector Control.

Connect the function described in F-22 Start

Speed [RPM] and F-29 Start Current in the

start delay time.

Regardless of the value applied by the

reference signal, the output speed applies

the setting of the start speed in F-22 Start

Speed [RPM] or F-23 Start Speed [Hz] and the

output current corresponds to the setting of

the start current in F-29 Start Current. This

function is typically used in hoisting

applications without counterweight and

especially in applications with a Cone-motor,

where the start is clockwise, followed by

rotation in the reference direction.

[4]

Horizontal

operation

Only possible with Advanced Vector Control.

For obtaining the function described in

F-22 Start Speed [RPM] and F-29 Start Current

during the start delay time. The motor

rotates in the reference direction. If the

reference signal equals zero (0), F-22 Start

Speed [RPM] is ignored and the output speed

equals zero (0). The output current

F-25 Start Function

Option:

Function:

corresponds to the setting of the start

current in F-29 Start Current.

[5]

Adv. Vector

Control/Flux

Clockwise

For the function described in F-22 Start Speed

[RPM] only. The start current is calculated

automatically. This function uses the start

speed in the start delay time only. Regardless

of the value set by the reference signal, the

output speed equals the setting of the start

speed in F-22 Start Speed [RPM]. [3] Start

speed/current clockwise and [5] Advanced

Vector Control/Flux clockwise are typically

used in hoisting applications. [4] Start speed/

current in reference direction is particularly

used in applications with counterweight and

horizontal movement.

[6]

Hoist Mech.

Brake Rel

For utilizing mechanical brake control

functions, B-24 Stop Delay to B-28 Gain Boost

Factor. This parameter is only active when

H-41 Motor Control Principle is set to [3] Flux

w/ motor feedback.

[7]

Adv. Vector

Control/Flux

Counter-cw

F-26 Motor Noise (Carrier Freq)

Select the carrier frequency. Changing the switching frequency

can help to reduce acoustic noise from the motor. Default

depends on power size.

Option:

Function:

[0]

1.0 kHz

[1]

1.5 kHz

Default switching frequency for

355-1200 kW / 500-1600 HP at 690

V

[2]

2.0 kHz

Default switching frequency for

250-800 kW / 350-1200 HP at

400/460 V and 37-315 kW / 50-450

HP at 690 V

[3]

2.5 kHz

[4]

3.0 kHz

Default switching frequency for

18.5-37 kW / 25-50 HP at 240 V and

37-200 kW / 50-300 HP at 400/460

V

[5]

3.5 kHz

[6]

4.0 kHz

Default switching frequency for

5.5-15 kW / 7.5-20 HP at 240 V and

11-30 kW / 15- 40 HP at 400/460 V

[7]

*

5.0 kHz

Default switching frequency for

0.25-3.7 kW / 0.33-5 HP at 200 V

and 0.37-7.5 kW / 0.5-10 HP at

400/460 V

[8]

6.0 kHz

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

37