O-56 preset reference select, 6 o-8# drive port diagnostics, 7 o-9# bus jog feedback – GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 93

Advertising
background image

O-54 Reversing Select

Option:

Function:

[0]

Digital

input

Select control of the frequency converter

reverse function via the terminals (digital

input) and/or via the fieldbus.

[1]

Bus

Activates the Reverse command via the serial

communication port or fieldbus optionmodule.

[2]

Logic AND

Activates the Reverse command via the

fieldbus/serial communication port, AND

additionally via one of the digital inputs.

[3]

*

Logic OR

Activates the Reverse command via the

fieldbus/serial communication port OR via one

of the digital inputs.

O-55 Set-up Select

Option:

Function:

Select control of the frequency converter set-

up selection via the terminals (digital input)

and/or via the network.

[0]

Digital

input

Activates the set-up selection via a digital

input.

[1]

Bus

Activates the set-up selection via the serial

communication port or network option

module.

[2]

Logic AND

Activates the set-up selection via the network/

serial communication port, AND additionally via

one of the digital inputs.

[3]

*

Logic OR

Activate the set-up selection via the network/

serial communication port OR via one of the

digital inputs.

O-56 Preset Reference Select

Option:

Function:

Select control of the frequency converter

Preset Reference selection via the terminals

(digital input) and/or via the network.

[0]

Digital

input

Activates Preset Reference selection via a

digital input.

[1]

Bus

Activates Preset Reference selection via the

serial communication port or network option

module.

[2]

Logic AND

Activates Preset Reference selection via the

network/serial communication port, AND

additionally via one of the digital inputs.

[3]

*

Logic OR

Activates the Preset Reference selection via the

network/serial communication port OR via one

of the digital inputs.

3.10.6 O-8# Drive Port Diagnostics

O-80 Bus Message Count

Range:

Function:

0

*

[0 - 0] This parameter shows the number of valid

messages detected on the network.

O-81 Bus Error Count

Range:

Function:

0

*

[0 - 0] This parameter shows the number of messages with

faults (e.g. CRC fault), detected on the network.

O-82 Slave Messages Rcvd

Range:

Function:

0

*

[0 - 0] This parameter shows the number of valid

messages addressed to the slave, sent by the

frequency converter.

O-83 Slave Error Count

Range:

Function:

0

*

[0 - 0] This parameter shows the number of error

messages, which could not be executed by the

frequency converter.

3.10.7 O-9# Bus Jog Feedback

Parameters to configure the Jog Speed when drive is in
Bus Control.

O-90 Bus Jog 1 Speed

Range:

Function:

100 RPM

*

[0 - par. F-17

RPM]

Enter the jog speed. Activate this

fixed jog speed via the serial port

or network option.

O-91 Bus Jog 2 Speed

Range:

Function:

200 RPM

*

[0 - par. F-17

RPM]

Enter the jog speed. Activate this

fixed jog speed via the serial port

or network option.

Parameter Descriptions

AF-650 GP Programming Guide

92

DET-618C