GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 30

Advertising
background image

The relation will depend on the type of unit selected in
K-30 Unit for Custom Readout:

Unit Type

Speed Relation

Dimensionless

Linear

Speed

Flow, volume

Flow, mass

Velocity

Length

Temperature

Pressure

Quadratic

Power

Cubic

Table 3.5

K-30 Unit for Custom Readout

Option:

Function:

It is possible to program a value to be shown in

the display of the keypad. The value will have a

linear, squared or cubed relation to speed. This

relation will depend on the unit selected (see

Table 3.5). The actual calculated value can be read

in DR-09 Custom Readout, and/or shown in the

display be selecting [DR-09] Custom Readout in

K-20 Display Line 1.1 Small to K-24 Display Line 3

Large.

[0]

*

None

[1]

%

[5]

PPM

[10]

1/min

[11]

rpm

[12]

Pulse/s

[20]

l/s

[21]

l/min

[22]

l/h

[23]

m3/s

[24]

m3/min

[25]

m3/h

[30]

kg/s

[31]

kg/min

[32]

kg/h

[33]

t/min

[34]

t/h

[40]

m/s

[41]

m/min

[45]

m

[60]

°C

[70]

mbar

[71]

bar

[72]

Pa

[73]

kPa

[74]

m WG

[80]

kW

[120] GPM

K-30 Unit for Custom Readout

Option:

Function:

[121] gal/s

[122] gal/min

[123] gal/h

[124] CFM

[125] ft3/s

[126] ft3/min

[127] ft3/h

[130] lb/s

[131] lb/min

[132] lb/h

[140] ft/s

[141] ft/min

[145] ft

[160] °F

[170] psi

[171] lb/in2

[172] in WG

[173] ft WG

[180] HP

K-31 Min Value of Custom Readout

Range:

Function:

0 CustomRea-

doutUnit

*

[-999999.99 -

par. K-32

CustomRea-

doutUnit]

This parameter sets the min.

value of the custom defined

readout (occurs at zero

speed). Only possible to set

different from 0 is when

selecting a linear unit in

K-30 Unit for Custom

Readout. For Quadratic and

Cubic units the minimum

value will be 0.

K-32 Max Value of Custom Readout

Range:

Function:

100 CustomRea-

doutUnit

*

[par. K-31 -

999999.99

CustomRea-

doutUnit]

This parameter sets the

max value to be shown

when the speed of the

motor has reached the set

value for F-17 Motor Speed

High Limit [RPM] or

F-15 Motor Speed High Limit

[Hz] (depends on setting in

K-02 Motor Speed Unit).

K-37 Display Text 1

Range:

Function:

0

*

[0 - 0] Enter a text which can be viewed in the graphical

display by selecting [37] Display Text 1 in

K-20 Display Line 1.1 Small, K-21 Display Line 1.2

Small, K-22 Display Line 1.3 Small, K-23 Display Line 2

Large or K-24 Display Line 3 Large.

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

29

3

3

Advertising