8 an-## analog in / out – GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 149

Advertising
background image

4.1.8 AN-## Analog In / Out

Par. No.
#

Parameter description

Default value

4-set-up

Change

during

operation

Conver-

sion

index

Type

AN-0#

AN-00

Live Zero Timeout Time

10 s

All set-ups

TRUE

0

Uint8

AN-01

Live Zero Timeout Function

[0] Off

All set-ups

TRUE

-

Uint8

AN-1#

AN-10

Terminal 53 Low Voltage

0.07 V

All set-ups

TRUE

-2

Int16

AN-11

Terminal 53 High Voltage

10 V

All set-ups

TRUE

-2

Int16

AN-12

Terminal 53 Low Current

0.14 mA

All set-ups

TRUE

-5

Int16

AN-13

Terminal 53 High Current

20 mA

All set-ups

TRUE

-5

Int16

AN-14

Terminal 53 Low Ref./Feedb. Value

0 ReferenceFeedbackUnit

All set-ups

TRUE

-3

Int32

AN-15

Terminal 53 High Ref./Feedb. Value

ExpressionLimit

All set-ups

TRUE

-3

Int32

AN-16

Terminal 53 Filter Time Constant

0.001 s

All set-ups

TRUE

-3

Uint16

AN-2#

AN-20

Terminal 54 Low Voltage

0.07 V

All set-ups

TRUE

-2

Int16

AN-21

Terminal 54 High Voltage

10 V

All set-ups

TRUE

-2

Int16

AN-22

Terminal 54 Low Current

0.14 mA

All set-ups

TRUE

-5

Int16

AN-23

Terminal 54 High Current

20 mA

All set-ups

TRUE

-5

Int16

AN-24

Terminal 54 Low Ref./Feedb. Value

0 ReferenceFeedbackUnit

All set-ups

TRUE

-3

Int32

AN-25

Terminal 54 High Ref./Feedb. Value

ExpressionLimit

All set-ups

TRUE

-3

Int32

AN-26

Terminal 54 Filter Time Constant

0.001 s

All set-ups

TRUE

-3

Uint16

AN-3#

AN-30

Terminal X30/11 Low Voltage

0.07 V

All set-ups

TRUE

-2

Int16

AN-31

Terminal X30/11 High Voltage

10 V

All set-ups

TRUE

-2

Int16

AN-34

Term. X30/11 Low Ref./Feedb. Value

0 ReferenceFeedbackUnit

All set-ups

TRUE

-3

Int32

AN-35

Term. X30/11 High Ref./Feedb. Value

ExpressionLimit

All set-ups

TRUE

-3

Int32

AN-36

Term. X30/11 Filter Time Constant

0.001 s

All set-ups

TRUE

-3

Uint16

AN-4#

AN-40

Terminal X30/12 Low Voltage

0.07 V

All set-ups

TRUE

-2

Int16

AN-41

Terminal X30/12 High Voltage

10 V

All set-ups

TRUE

-2

Int16

AN-44

Term. X30/12 Low Ref./Feedb. Value

0 ReferenceFeedbackUnit

All set-ups

TRUE

-3

Int32

AN-45

Term. X30/12 High Ref./Feedb. Value

ExpressionLimit

All set-ups

TRUE

-3

Int32

AN-46

Term. X30/12 Filter Time Constant

0.001 s

All set-ups

TRUE

-3

Uint16

AN-5#

AN-50

Terminal 42 Output

ExpressionLimit

All set-ups

TRUE

-

Uint8

AN-51

Terminal 42 Output Min Scale

0 %

All set-ups

TRUE

-2

Int16

AN-52

Terminal 42 Output Max Scale

100 %

All set-ups

TRUE

-2

Int16

AN-53

Terminal 42 Output Bus Control

0 %

All set-ups

TRUE

-2

N2

AN-54

Terminal 42 Output Timeout Preset

0 %

1 set-up

TRUE

-2

Uint16

AN-55

Terminal 42 Output Filter

[0] Off

1 set-up

TRUE

-

Uint8

AN-6#

AN-60

Terminal X30/8 Output

ExpressionLimit

All set-ups

TRUE

-

Uint8

AN-61

Terminal X30/8 Min. Scale

0 %

All set-ups

TRUE

-2

Int16

AN-62

Terminal X30/8 Max. Scale

100 %

All set-ups

TRUE

-2

Int16

AN-63

Terminal X30/8 Bus Control

0 %

All set-ups

TRUE

-2

N2

AN-64

Terminal X30/8 Output Timeout Preset

0 %

1 set-up

TRUE

-2

Uint16

Parameter Lists

AF-650 GP Programming Guide

148

DET-618C