3.15 RS-## Resolver Interface

RS-50 Poles

Range:

Function:

2

*

[2 - 8]

Set the number of poles on the resolver.

The value is stated in the data sheet for resolvers.

RS-51 Input Voltage

Range:

Function:

7 V

*

[2 - 8 V] Set the input voltage to the resolver. The

voltage is stated as RMS value.

The value is stated in the data sheet for

resolvers

RS-52 Input Frequency

Range:

Function:

10 kHz

*

[2 - 15 kHz] Set the input frequency to the resolver.

The value is stated in the data sheet for

resolvers.

RS-53 Transformation Ratio

Range:

Function:

0.5

*

[0.1 - 1.1] Set the transformation ratio for the resolver.

The transformation ration is:

Tratio

=

VOut

VIn

The value is stated in the data sheet for

resolvers.

RS-59 Resolver Interface

Activate the OPCRES resolver option when the resolver

parameters are selected.

To avoid damage to resolvers RS-50 PolesRS-53 Transformation

Ratio must be adjusted before activating this parameter.

Option:

Function:

[0]

*

Disabled

[1]

Enabled

3.16 Parameter Data Check

3.16.1 Last 10 Changes

Displays a list of the 10 last changes made to the
parameters in the present parameter setup. This allows for
any corrections of the last 10 changes.

3.16.2 Since Factory Settings

Displays a list of all the parameter changes since the
factory settings of the drive or since the last factory restore
of parameters.

3.17 ID-##

Drive

Information

Parameter group related to drive information such as
operating data, hardware configuration and software
version.

3.17.1 ID-0# Operating Data

Parameters to view operating hours. kWh counters, power
ups, etc.

ID-00 Operating hours

Range:

Function:

0 h

*

[0 - 2147483647 h] View how many hours the frequency

converter has run. The value is saved

when the frequency converter is

turned off.

ID-01 Running Hours

Range:

Function:

0 h

*

[0 - 2147483647

h]

View how many hours the motor has

run. Reset the counter in ID-07 Reset

Running Hours Counter. The value is

saved when the frequency converter is

turned off.

ID-02 kWh Counter

Range:

Function:

0 kWh

*

[0 - 2147483647

kWh]

Registering the power consumption

of the motor as a mean value over

one hour. Reset the counter in

ID-06 Reset kWh Counter.

ID-03 Power Up's

Range:

Function:

0

*

[0 - 2147483647] View the number of times the frequency

converter has been powered up.

ID-04 Over Temp's

Range:

Function:

0

*

[0 - 65535] View the number of frequency converter

temperature faults which have occurred.

ID-05 Over Volt's

Range:

Function:

0

*

[0 - 65535] View the number of frequency converter

overvoltages which have occurred.

ID-06 Reset kWh Counter

Option:

Function:

[0]

*

Do not reset

Nno reset of the kWh counter is desired.

[1]

Reset counter Press [OK] to reset the kWh counter to zero

(see ID-02 kWh Counter).