3.9 SP-## Special Functions

Parameter group related to special functions with regards
to Line Voltage, Reset Functions, Current Limit, Energy
Savings, Derating, and Accel/Decel Ramp Types.

SP-00 Fault Level

Option:

Function:

[0]

*

Off

Use this parameter to customize Fault levels. Use

[0] Off with caution as it will ignore all Warnings

& Alarms for the chosen source.

[1]

Warning

[2]

Trip

[3]

Trip Lock

Failure

Alarm

Off

Warning

Trip

Trip Lock

10 V low

1

X

D

24 V low

47

X

D

1.8 V supply low

48

X

D

Voltage limit

64

X

D

Earth fault during ramping

14

D

X

Earth fault 2 during cont. operation

45

D

X

Torque Limit

12

X

D

Over Current

13

X

D

Short Circuit

16

X

D

Heatsink temperature

29

X

D

Heatsink sensor

39

X

D

Control card temperature

65

X

D

Power card temperature

69

1)

X

D

Heatsink temperature

1)

244

X

D

Heatsink sensor

1)

245

X

D

Power card temperature

1)

247

Table 3.16 Table for Selection of Choice of Action when Selected Alarm Appears

D = Default setting

x = possible selection

1) Only drives 125 HP and above. All others is just a warning.