Motor power [kw, Base speed, P-07 motor – GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 58: Power [kw, 6 base speed, P-07 motor power [kw, P-06 base speed, 2 p-2# motor selection

Advertising
background image

P-05 Motor Cont. Rated Torque

Range:

Function:

0.1 Nm

*

[0.1 -

10000 Nm]

Enter the value from the motor nameplate

data. The default value corresponds to the

nominal rated output. This parameter is

available when P-20 Motor Construction is

set to [1] PM, non salient SPM, i.e. the

parameter is valid for PM and non-salient

SPM motors only.

P-06 Base Speed

Range:

Function:

1420

RPM

*

[10 - 60000

RPM]

Enter the nominal motor speed value

from the motor nameplate data. The

data are used for calculating motor

compensations. n

m,n

= n

s

- n

slip

.

P-07 Motor Power [kW]

Range:

Function:

4.00

kW

*

[0.09 -

3000.00

kW]

NOTE

This parameter cannot be adjusted
while the motor is running.

Enter the nominal motor power in kW

according to the motor nameplate data.

The default value corresponds to the

nominal rated output of the unit.

This parameter is visible in keypad if

K-03 Regional Settings is [0] International.

NOTE

Four sizes down, one size up from
nominal unit rating.

P-09 Slip Compensation

Range:

Function:

100

%

*

[-500 -

500 %]

Enter the % value for slip compensation, to

compensate for tolerances in the value of n

M,N

.

Slip compensation is calculated automatically,

i.e. on the basis of the rated motor speed n

M,N

.

This function is not active when H-40 Configu-

ration Mode is set to [1] Speed closed loop or

[2] Torque Torque control with speed feedback

or when H-41 Motor Control Principle is set to

[0] U/f special motor mode.

P-10 Slip Compensation Time Constant

Range:

Function:

0.10 s

*

[0.05 - 5 s] Enter the slip compensation reaction speed.

A high value results in slow reaction, and a

low value results in quick reaction. If low-

frequency resonance problems arise, use a

longer time setting.

NOTE

P-10 Slip Compensation Time Constant will not have effect
when P-20 Motor Construction = [1] PM, non salient SPM.

3.6.2 P-2# Motor Selection

Parameters to configure the drive to work with
Asynchronous AC Motor or Permanent Magnet Motor

P-20 Motor Construction

Option:

Function:

Select the motor design type.

[0]

*

Asynchron

For asynchronous motors.

[1]

PM, non salient

SPM

For salient or non-salient PM motors.

PM motors are divided into two groups,

with either surface mounted (non salient)

or interior (salient) magnets.

P-24 Damping Gain

Range:

Function:

140

%

*

[0 -

250 %]

The damping gain will stabilize the PM machine

in order to run the PM machine smooth and

stable. The value of Damping gain will control

the dynamic performance of the PM machine.

High damping gain will give high dynamic

performance and low damping gain will give low

dynamic performance. The dynamic performance

is related to the machine data and load type. If

the damping gain is too high or low the control

will become unstable.

P-25 Low Speed Filter Time Const.

Range:

Function:

0.01 s

*

[0.01 - 20 s] This time constant is used below 10%

rated speed. Obtain quick control through

a short damping time constant. However,

if this value is too short, the control gets

unstable.

P-26 High Speed Filter Time Const.

Range:

Function:

0.01 s

*

[0.01 - 20 s] This time constant is used above 10%

rated speed. Obtain quick control through

a short damping time constant. However,

if this value is too short, the control gets

unstable.

P-27 Voltage filter time const.

Range:

Function:

0.001 s

*

[0.001 - 1 s] Reduces the influence of high frequency

ripple and system resonance in the

calculation of supply voltage. Without

this filter, the ripples in the currents can

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

57

3

3

Advertising