GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 28

Advertising
background image

[1200] Control Word

Present control word

[1201] Reference [Unit]

Total reference (sum of digital/

analog/preset/bus/freeze ref./catch

up and slow-down) in selected unit.

[1202] Reference %

Total reference (sum of digital/

analog/preset/bus/freeze ref./catch

up and slow-down) in percent.

[1203] Status Word

Present status word.

[1205] Main Actual Value

[%]

Actual value as a percentage.

[1209] Custom Readout

[1210] Power [kW]

Actual power consumed by the

motor in kW.

[1211] Power [hp]

Actual power consumed by the

motor in HP.

[1212] Motor Voltage

Voltage supplied to the motor.

[1213] Frequency

Motor frequency, i.e. the output

frequency from the frequency

converter in Hz

[1214] Motor Current

Phase current of the motor

measured as effective value.

[1215] Frequency [%]

Motor frequency, i.e. the output

frequency from the frequency

converter in percent.

[1216] Torque

Actual motor torque in Nm

[1217] Speed [RPM]

Speed in RPM (revolutions per

minute) i.e. the motor shaft speed in

closed loop.

[1218] Motor Thermal

Thermal load on the motor,

calculated by the Electronic Thermal

Overload function.

[1219] KTY Sensor

Temperature

[1220] Motor Angle

[1221] Phase Angle

[1222] Torque %

Present motor load as a percentage

of the rated motor torque.

[1230] DC Link Voltage

Intermediate circuit voltage in the

frequency converter.

[1232] BrakeEnergy/s

Present brake power transferred to

an external brake resistor.

Stated as an instantaneous value.

[1233] BrakeEnergy/2 min

Brake power transferred to an

external brake resistor. The mean

power is calculated continuously for

the most recent 120 seconds.

[1234] Heatsink Temp.

Present heat sink temperature of the

frequency converter. The cut-out

limit is 95

±5 ±°C; cutting back in

occurs at 70

±5° C.

[1235] Inverter Thermal

Percentage load of the inverters.

[1236] Inv. Nom. Current

Nominal current of the frequency

converter.

[1237] Inv. Max. Current

Maximum current of the frequency

converter.

[1238] Logic Controller

State

State of the event executed by the

control.

[1239] Control Card Temp.

Temperature of the control card.

[1250] External Reference

Sum of the external reference as a

percentage, i.e. the sum of analog/

pulse/bus.

[1251] Pulse Reference

Frequency in Hz connected to the

digital inputs (18, 19 or 32, 33).

[1252] Feedback [Unit]

Reference value from programmed

digital input(s).

[1253] Digi Pot Reference

[1260] Digital Input

Signal states form the 6 digital

terminals (18, 19, 27, 29, 32 and 33).

Input 18 corresponds to the bit at

the far left. Signal low = 0; Signal

high = 1.

[1261] Terminal 53 Switch

Setting

Setting of input terminal 54. Current

= 0; Voltage = 1.

[1262] Analog Input 53

Actual value at input 53 either as a

reference or protection value.

[1263] Terminal 54 Switch

Setting

Setting of input terminal 54. Current

= 0; Voltage = 1.

[1264] Analog Input 54

Actual value at input 54 either as

reference or protection value.

[1265] Analog Output 42

[mA]

Actual value at output 42 in mA.

Use AN-50 Terminal 42 Output to

select the value to be shown.

[1266] Digital Output [bin]

Binary value of all digital outputs.

[1267] Freq. Input #29 [Hz] Actual value of the frequency

applied at terminal 29 as an impulse

input.

[1268] Freq. Input #33 [Hz] Actual value of the frequency

applied at terminal 33 as an impulse

input.

[1269] Pulse Output #27

[Hz]

Actual value of impulses applied to

terminal 27 in digital output mode.

[1270] Pulse Output #29

[Hz]

Actual value of impulses applied to

terminal 29 in digital output mode.

[1271] Relay Output [bin]

[1272] Counter A

Application dependent (e.g. LC

Control)

[1273] Counter B

Application dependent (e.g. LC

Control)

[1274] Prec. Stop Counter

Display the actual counter value.

[1275] Analog input

X30/11

Actual value at input X30/11 either

as reference or protection value.

[1276] Analog input

X30/12

Actual value at input X30/12 either

as reference or protection value.

[1277] Analog output

X30/8 mA

Actual value at output X30/8 in mA.

Use AN-60 Terminal X30/8 Output to

select the value to be shown.

[1280] Fieldbus CTW 1

Control word (CTW) received from

the Bus Master.

[1282] Fieldbus REF 1

Main reference value sent with

control word from the Bus Master.

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

27