LC-52 Logic Controller Action

Array [20]

Option:

Function:

[14]

Select preset ref

4

Selects preset reference 4.

If the active preset reference is changed,

it will merge with other preset reference

commands coming from either the digital

inputs or via a Network.

[15]

Select preset ref

5

Selects preset reference 5.

If the active preset reference is changed,

it will merge with other preset reference

commands coming from either the digital

inputs or via a Network.

[16]

Select preset ref

6

Selects preset reference 6.

If the active preset reference is changed,

it will merge with other preset reference

commands coming from either the digital

inputs or via a Network.

[17]

Select preset ref

7

Selects preset reference 7.

If the active preset reference is changed,

it will merge with other preset reference

commands coming from either the digital

inputs or via a Network.

[18]

Select Accel/

Decel 1

Selects ramp 1.

[19]

Select Accel/

Decel 2

Selects ramp 2.

[20]

Select Accel/

Decel 3

Selects ramp 3.

[21]

Select Accel/

Decel 4

Selects ramp 4.

[22]

Run

Issues a start command to the frequency

converter.

[23]

Run reverse

Issues a start reverse command to the

frequency converter.

[24]

Stop

Issues a stop command to the frequency

converter.

[25]

Qstop

Issues a quick stop command to the

frequency converter.

[26]

Dcstop

Issues a DC stop command to the

frequency converter.

[27]

Coast

The frequency converter coasts

immediately. All stop commands

including the coast command stop the

Logic Controller.

[28]

Freeze output

Freezes the output frequency of the

frequency converter.

[29]

Start timer 0

Starts timer 0, see LC-20 Logic Controller

Timer for further description.

[30]

Start timer 1

Starts timer 1, see LC-20 Logic Controller

Timer for further description.

LC-52 Logic Controller Action

Array [20]

Option:

Function:

[31]

Start timer 2

Starts timer 2, see LC-20 Logic Controller

Timer for further description.

[32]

Set digital out A

low

Any output with LC output A will be low.

[33]

Set digital out B

low

Any output with LC output B will be low.

[34]

Set digital out C

low

Any output with LC output Cwill be low.

[35]

Set digital out D

low

Any output with LC output D will be low.

[36]

Set digital out E

low

Any output with LC output E will be low.

[37]

Set digital out F

low

Any output with LC output F will be low.

[38]

Set digital out A

high

Any output with LC output A will be

high.

[39]

Set digital out B

high

Any output with LC output B will be

high.

[40]

Set digital out C

high

Any output with LC output C will be

high.

[41]

Set digital out D

high

Any output with LC output D will be

high.

[42]

Set digital out E

high

Any output with LC output E will be

high.

[43]

Set digital out F

high

Any output with LC output Fwill be high.

[60]

Reset Counter A

Resets Counter A to zero.

[61]

Reset Counter B

Resets Counter B to zero.

[70]

Start timer 3

Start Timer 3, see LC-20 Logic Controller

Timer for further description.

[71]

Start timer 4

Start Timer 4, see LC-20 Logic Controller

Timer for further description.

[72]

Start timer 5

Start Timer 5, see LC-20 Logic Controller

Timer for further description.

[73]

Start timer 6

Start Timer 6, see LC-20 Logic Controller

Timer for further description.

[74]

Start timer 7

Start Timer 7, see LC-20 Logic Controller

Timer for further description.

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

127

3

3