3.10.2 O-1# Control Settings

Parameters to configure the option control word profile.

O-10 Control Word Profile

Select the interpretation of the control and status words

corresponding to the installed fieldbus. Only the selections valid

for the fieldbus installed in slot A will be visible in the keypad

display.

For guidelines in selection of GE Drive profile and [1] PROFIdrive

profile refer to the design guide of the related product.

For additional guidelines in the selection of [1] PROFIdrive profile

and [5] ODVA , see Operating Instructions for the installed

fieldbus.

Option:

Function:

[0]

*

Drive Profile

[1]

PROFIdrive profile

[5]

ODVA

O-13 Configurable Status Word STW

Option:

Function:

This parameter enables configuration of bits

12–15 in the status word.

[0]

No function

[1]

*

Profile Default Function corresponds to the profile default

selected in O-10 Control Word Profile.

O-14 Configurable Control Word CTW

Option:

Function:

Selection of control word bit 10 if it is active

low or active high.

[0]

None

[1]

*

Profile

default

[2]

CTW Valid,

active low

[4]

PID error

inverse

When enabled, it inverts the resulting error

from the process PID controller. Available

only if "Configuration Mode" is set to

"Surface Winder", "Extended PID Speed OL"

or "Extended PID Speed CL".

[5]

PID reset I

part

When enabled, resets the I-part of the

Process PID controller. Equivalent to

PI-40 Process PID I-part Reset. Available only if

"Configuration Mode" is set to "Surface

Winder", "Extended PID Speed OL" or

"Extended PID Speed CL".

[6]

PID enable

When enabled, enables the extended process

PID controller. Equivalent to PI-50 Process PID

Extended PID. Available only if "Configuration

Mode" is set "Extended PID Speed OL" or

"Extended PID Speed CL".

3.10.3 O-3# Drive Port Settings

Parameters to configure the GE drive port.

O-30 Protocol

Option:

Function:

[0]

Drive

Communication according to the Drive

Protocol.

[1]

Drive MC

Select the protocol for the drive (standard)

port.

[2]

*

Modbus RTU

O-31 Address

Range:

Function:

1

*

[1 - 255]

Enter the address for the Drive (standard) port.

Valid range: 1-126.

O-32 Drive Port Baud Rate

Option:

Function:

[0]

2400 Baud

Baud rate selection for the Drive (standard)

port.

[1]

4800 Baud

[2]

*

9600 Baud

[3]

19200 Baud

[4]

38400 Baud

[5]

57600 Baud

[6]

76800 Baud

[7]

115200 Baud

O-33 Drive Port Parity

Option:

Function:

Parity and Stop Bits for the protocol

O-30 Protocol using the Drive Port.

For some of the protocols, not all

options are visible. Default depends

on the protocol selected.

[0]

*

Even Parity, 1 Stop Bit

[1]

Odd Parity, 1 Stop Bit

[2]

No Parity, 1 Stop Bit

[3]

No Parity, 2 Stop Bits

O-34 Estimated cycle time

Range:

Function:

0 ms

*

[0 - 1000000

ms]

In noisy environments, the interface may

be blocked by due to overload of bad

frames. This parameter specifies the time

between two consecutive frames on the

network. If the interface does not detect

valid frames in that time it flushes the

receive buffer.

Parameter Descriptions

AF-650 GP Programming Guide

88

DET-618C