NOTE

If [1] S-ramp Const Jerk is selected and the reference during
ramping is changed the ramp time may be prolonged in
order to realize a jerk free movement which may result in
a longer start or stop time.
Additional adjustment of the S-ramp ratios or switching
initiators may be necessary.

For each of four ramps (parameter groups F-0#, E-1#, H-0#,
SP-7#, SP-8# and SP-9#) configure the ramp parameters:
ramp type, ramping times (duration of acceleration and
deceleration) and level of jerk compensation for S ramps.

Start by setting the linear ramping times corresponding to
the figures.

If S-ramps are selected then set the level of non-linear jerk
compensation required. Set jerk compensation by defining
the proportion of accel and decel times where acceleration
and deceleration are variable (i.e. increasing or decreasing).
The S-ramp acceleration and deceleration settings are
defined as a percentage of the actual ramp time.

H-08 Reverse Lock

Option:

Function:

NOTE

This parameter cannot be adjusted while
the motor is running.

Select the motor speed direction(s) required.

Use this parameter to prevent unwanted

reversing. When H-40 Configuration Mode is set

to [3] Process, H-08 Reverse Lock is set to [0]

Clockwise as default. The setting in

H-08 Reverse Lock does not limit options for

setting F-15 Motor Speed High Limit [Hz] or

F-17 Motor Speed High Limit [RPM].

[0]

*

Clockwise

The reference is set to CW rotation. Reversing

input (Default term 19) must be open.

[1]

Counter

clockwise

The reference is set to CCW rotation.

Reversing input (Default term 19) must be

closed. If Reversing is required with ‘Reverse’

input is open the motor direction can be

changed by H-48 Clockwise Direction

[2]

Both

directions

Allows the motor to rotate in both directions.

H-09 Start Mode

Option:

Function:

NOTE

This parameter cannot be adjusted
while motor is running.

H-09 Start Mode

Option:

Function:

This function makes it possible to catch a

motor which is spinning freely due to a

mains drop-out.

[0]

*

Disabled

No function

[1]

Enabled

Enables the frequency converter to “catch”

and control a spinning motor.

When H-09 Start Mode is enabled,

F-24 Holding Time and F-25 Start Function

have no function.

[2]

Enabled Always

[3]

Enabled Ref.

Dir.

[4]

Enab. Always

Ref. Dir.

NOTE

This function is not recommended for hoisting
applications.

3.7.2 H-2# Motor Feedback Monitoring

Parameters to configure Motor Feedback Monitoring.

H-20 Motor Feedback Loss Function

Option:

Function:

This function is used to monitor for

consistency in feedback signal, i.e. if

the feedback signal is available.

Select which reaction the frequency

converter should take if a feedback

fault is detected. The selected action

is to take place when the feedback

signal differs from the output speed

by the value set in H-21 Motor

Feedback Speed Error for longer than

the value set inH-22 Motor Feedback

Loss Timeout.

[0]

Disabled

[1]

Warning

[2]

*

Trip

[3]

Jog

[4]

Freeze Output

[5]

Max Speed

[6]

Switch to Open

Loop

[7]

Select Setup 1

[8]

Select Setup 2

[9]

Select Setup 3

[10]

Select Setup 4

[11]

stop & trip

Warning 90 is active as soon as the value in H-21 Motor
Feedback Speed Error
is exceeded, regardless of the setting

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

61

3