B-15 Brake Check

Option:

Function:

amplitude before braking + 1%: Brake

check has failed by returning a warning

or alarm.

4.

If the DC link ripple amplitude while

braking is higher than the DC link

ripple amplitude before braking + 1%:

Brake check is OK.

[0]

*

Off

Monitors brake resistor and brake IGBT for a

short-circuit during operation. If a short-circuit

occurs, warning 25 appears.

[1]

Warning

Monitors brake resistor and brake IGBT for a

short-circuit, and runs a test for brake resistor

disconnection during power-up.

[2]

Trip

Monitors for a short-circuit or disconnection of

the brake resistor, or a short-circuit of the brake

IGBT. If a fault occurs, the frequency converter

cuts out while displaying an alarm (trip locked).

[3]

Stop and

trip

Monitors for a short-circuit or disconnection of

the brake resistor, or a short-circuit of the brake

IGBT. If a fault occurs, the frequency converter

decels to coast and then trips. A trip lock alarm

is displayed (e.g. warning 25, 27 or 28).

[4]

AC brake

Monitors for a short-circuit or disconnection of

the brake resistor, or a short-circuit of the brake

IGBT. If a fault occurs, the frequency converter

performs a controlled decel.

[5]

Trip Lock

NOTE

Remove a warning arising in connection with [0] Off or [1]
Warning
by cycling the mains supply. The fault must be
corrected first. For [0] Off or [1] Warning, the frequency
converter keeps running even if a fault is located.

This parameter is only active in frequency converters with
an integral dynamic brake.

B-16 AC brake Max. Current

Range:

Function:

100 %

*

[0 - 1000.0 %] Enter the maximum permissible current

when using AC brake to avoid

overheating of motor windings.

NOTE

B-16 AC brake Max. Current will not have effect when
P-20 Motor Construction = [1] PM, non salient SPM.

B-17 Over-voltage Control

Option:

Function:

Over-voltage control (OVC) reduces the risk

of the frequency converter tripping due to

an over voltage on the DC link caused by

generative power from the load.

[0]

*

Disabled

No OVC required.

[1]

Enabled (not

at stop)

Activates OVC except when using a stop

signal to stop the frequency converter.

[2]

Enabled

Activates OVC.

NOTE

OVC must not be enabled in hoisting applications.

B-18 Brake Check Condition

Range:

Function:

[0]

*

At Power Up

Brake check will be performed at

power up

[1]

After Coast Situations Brake check will be performed after

coast situations

Parameter Descriptions

AF-650 GP Programming Guide

130

DET-618C