3.8 AN-## Analog In/Out

Parameter group related to the Analog Inputs and
Outputs.

3.8.1 AN-0# Analog I/O Mode

Parameters to configure the Analog Inputs and Output
time out period for lost signals.

AN-00 Live Zero Timeout Time

Range:

Function:

10 s

*

[1 -

99 s]

Enter the Live Zero Time-out time period. Live

Zero Time-out Time is active for analog inputs, i.e.

terminal 53 or terminal 54, used as reference or

feedback sources. If the reference signal value

associated with the selected current input falls

below 50% of the value set in AN-10 Terminal 53

Low Voltage, AN-12 Terminal 53 Low Current,

AN-20 Terminal 54 Low Voltage or AN-22 Terminal

54 Low Current for a time period longer than the

time set in AN-00 Live Zero Timeout Time, the

function selected in AN-01 Live Zero Timeout

Function will be activated.

AN-01 Live Zero Timeout Function

Option:

Function:

Select the time-out function. The function set

in AN-01 Live Zero Timeout Function will be

activated if the input signal on terminal 53 or

54 is below 50% of the value in

AN-10 Terminal 53 Low Voltage, AN-12 Terminal

53 Low Current, AN-20 Terminal 54 Low Voltage

or AN-22 Terminal 54 Low Current for a time

period defined in AN-00 Live Zero Timeout

Time. If several time-outs occur simultaneously,

the frequency converter prioritises the time-

out functions as follows:

1.

AN-01 Live Zero Timeout Function

2.

O-04 Control Word Timeout Function

[0]

*

Off

[1]

Freeze

output

Frozen at the present value

[2]

Stop

Overruled to stop

[3]

Jogging

Overruled to jog speed

[4]

Max. speed

Overruled to max. speed

[5]

Stop and

trip

Overruled to stop with subsequent trip

[20]

Coast

Coast: Overruled to Coast

[21]

Coast and

trip

Coast and trip: Overruled to Coast with

subsequent trip.

3.8.2 AN-1# Analog Input 53

Parameters to configure the scaling and limits for Analog
Input 1 (terminal 53)

AN-10 Terminal 53 Low Voltage

Range:

Function:

0.07 V

*

[-10.00 - par.

AN-11 V]

Enter the low voltage value. This analog

input scaling value should correspond to

the minimum reference value, set in

AN-14 Terminal 53 Low Ref./Feedb. Value.

See also the section Reference Handling.

AN-11 Terminal 53 High Voltage

Range:

Function:

10 V

*

[par. AN-10 -

10 V]

Enter the high voltage value. This analog

input scaling value should correspond to

the high reference/feedback value set in

AN-15 Terminal 53 High Ref./Feedb. Value.

AN-12 Terminal 53 Low Current

Range:

Function:

0.14

mA

*

[0 - par.

AN-13 mA]

Enter the low current value. This

reference signal should correspond to the

minimum reference value, set in

F-52 Minimum Reference. The value must

be set at >2 mA in order to activate the

Live Zero Time-out Function in AN-01 Live

Zero Timeout Function.

AN-13 Terminal 53 High Current

Range:

Function:

20 mA

*

[par. AN-12 -

20 mA]

Enter the high current value

corresponding to the high reference/

feedback set in AN-15 Terminal 53

High Ref./Feedb. Value.

AN-14 Terminal 53 Low Ref./Feedb. Value

Range:

Function:

0

*

[-999999.999 -

999999.999]

Enter the analog input scaling value

that corresponds to the low

voltage/low current set in

AN-10 Terminal 53 Low Voltage and

AN-12 Terminal 53 Low Current.

AN-15 Terminal 53 High Ref./Feedb. Value

Range:

Function:

1500.000 Referen-

ceFeedbackUnit

*

[-999999.999 -

999999.999

ReferenceFeed-

backUnit]

Enter the analog input

scaling value that

corresponds to the

maximum reference

feedback value set in

AN-11 Terminal 53 High

Voltage and

Parameter Descriptions

AF-650 GP Programming Guide

72

DET-618C