Illustration 3.46, 2 pi-1# torque pi control, 3 pi-2# proces pid feedback – GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 136

Advertising
background image

NOTE

Severe filtering can be detrimental to dynamic
performance.
This parameter is used with H-40 Configuration Mode [1]
Speed closed loop
and [2] Torque control.
The filter time in flux sensorless must be adjusted to
3-5 ms.

Illustration 3.46 Feedback Signal

PI-07 Speed PID Feedback Gear Ratio

Range:

Function:

1

*

[0.0001 - 32.0000]

Illustration 3.47

PI-08 Speed PID Feed Forward Factor

Range:

Function:

0 %

*

[0 - 500 %] The reference signal bypasses the speed

controller by the amount specified. This

feature increases the dynamic performance

of the speed control loop.

3.21.2 PI-1# Torque PI Control

PI-12 Torque PI Proportional Gain

Range:

Function:

100 %

*

[0 - 500 %] Enter the proportional gain value for the

torque controller. Selection of a high value

makes the controller react faster. Too high

a setting leads to controller instability.

PI-13 Torque PI Integration Time

Range:

Function:

0.020 s

*

[0.002 - 2 s] Enter the integration time for the torque

controller. Selection of a low value makes

the controller react faster. Too low a

setting leads to control instability.

3.21.3 PI-2# Proces PID Feedback

Parameters to configure the feedback sources for the
Process PID Control.

PI-20 Process CL Feedback 1 Resource

Option:

Function:

The effective feedback signal is made

up of the sum of up to two different

input signals.

Select which frequency converter

input should be treated as the source

Parameter Descriptions