SP-10 Line failure

Option:

Function:

Illustration 3.39 [7] Kinetic Back-Up, trip with

recovery where mains return below SP-15 Kin.

Backup Trip Recovery Level. In this illustration a

quick ramp is used.

A

Normal Operation

B

Mains failure

C

Kinetic back-up

D

Mains return

E

Kinetic back-up ramping to trip

F

Trip

Table 3.21 Legend to Illustration 3.39

SP-11 Line Voltage at Input Fault

Range:

Function:

342 V

*

[180 -

600 V]

This parameter defines the threshold voltage

at which the selected function in SP-10 Line

failure should be activated. It may be

considered to choose 90% of the nominal

mains as the detection level, depending on

the supply quality. For a supply of 380 V

SP-11 Line Voltage at Input Fault should thus

be set to 342 V. This results in a DC detection

level of 462 V (SP-11 Line Voltage at Input Fault

* 1.35)

SP-12 Function at Line Imbalance

Operation under severe main imbalance conditions reduces the

lifetime of the motor. Conditions are considered severe if the

motor is operated continuously near nominal load (e.g. a pump

or fan running near full speed).

Option:

Function:

[0]

*

Trip

Trips the frequency

converter

[1]

Warning

Issues a warning

[2]

Disabled

No action

SP-13 Mains Failure Step Factor

Range:

Function:

1

*

[0 - 5]

SP-14 Kin. Backup Time Out

Range:

Function:

60 s

*

[0 - 60

s]

This parameter defines the Kinetic Backup Time

Out in flux mode when running on low voltage

grids. If the supply voltage does not increase

above the value defined in SP-11 Line Voltage at

Input Fault +5% within the specified time, the

drive will then automatically run a controlled

ramp-down profile before stopping.

SP-15 Kin. Backup Trip Recovery Level

Range:

Function:

60000.000 Referen-

ceFeedbackUnit

*

[0 - 60000.000

ReferenceFeed-

backUnit]

This parameter

specifies the Kinetic

Backup Trip

Recovery Level. The

unit is defined in

K-02 Motor Speed

Unit.

3.9.2 SP-2# Reset Functions

Parameters to configure the trip delay do to Torque Limit
or Drive Fault.

SP-24 Trip Delay at Current Limit

Range:

Function:

60 s

*

[0 - 60

s]

Enter the current limit trip delay in seconds.

When the output current reaches the current

limit (F-43 Current Limit), a warning is triggered.

When the current limit warning has been contin-

uously present for the period specified in this

parameter, the frequency converter trips. Disable

the trip delay by setting the parameter to 60 s =

OFF. Thermal monitoring of the frequency

converter will still remain active.

SP-25 Trip Delay at Torque Limit

Range:

Function:

60 s

*

[0 - 60

s]

Enter the torque limit trip delay in seconds.

When the output torque reaches the torque

limits (F-40 Torque Limiter (Driving) and

F-41 Torque Limiter (Braking)), a warning is

triggered. When the torque limit warning has

been continuously present for the period

specified in this parameter, the frequency

converter trips. Disable the trip delay by setting

the parameter to 60 s = Off. Thermal monitoring

of the frequency converter will still remain active.

SP-26 Trip Delay at Drive Fault

Range:

Function:

0 s

*

[0 - 35 s] When the frequency converter detects an over-

voltage in the set time trip will be effected after

the set time.

Parameter Descriptions

AF-650 GP Programming Guide

80

DET-618C

3