C-10 comparator operand, Lc-10 comparator operand, 2 lc-1# comparators – GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 122

Advertising
background image

LC-02 Stop Event

Select the boolean (TRUE or FALSE) input to deactivate Logic

Controller.

Option:

Function:

[74]

Logic Controller Time-out 7 Logic Controller timer 7 is

timed out.

[75]

Start command given

[76]

Digital input x30 2

[77]

Digital input x30 3

[78]

Digital input x30 4

[94]

RS Flipflop 0

See parameter group LC-1#

Comparators

[95]

RS Flipflop 1

See parameter group LC-1#

Comparators

[96]

RS Flipflop 2

See parameter group LC-1#

Comparators

[97]

RS Flipflop 3

See parameter group LC-1#

Comparators

[98]

RS Flipflop 4

See parameter group LC-1#

Comparators

[99]

RS Flipflop 5

See parameter group LC-1#

Comparators

[100] RS Flipflop 6

See parameter group LC-1#

Comparators

[101] RS Flipflop 7

See parameter group LC-1#

Comparators

LC-03 Reset Logic Controller

Option:

Function:

[0]

*

Do not reset Logic

Controller

Retains programmed settings in all

parameter group LC-## Logic

Controller.

[1]

Reset Logic

Controller

Resets all parameters in parameter

group LC-## Logic Controller to default

settings.

3.19.2 LC-1# Comparators

Parameters to configure the Logic Controller (LC)
comparators. Comparators are used for comparing
variables with fixed preset values.

LC-10 Comparator Operand

Array [6]

Option:

Function:

Choices [1] to [31] are variables which

will be compared based on their

values. Choices [50] to [186] are digital

values (TRUE/FALSE) where the

comparison is based on the amount

of time during which they are set to

LC-10 Comparator Operand

Array [6]

Option:

Function:

TRUE or FALSE, respectively. See

LC-11 Comparator Operator.

Select the variable to be monitored by

the comparator.

[0]

*

DISABLED

The comparator is disabled.

[1]

Reference

The resulting remote reference (not

local) as a percentage.

[2]

Feedback

In the unit [RPM] or [Hz]

[3]

Motor speed

[RPM] or [Hz]

[4]

Motor Current

[A]

[5]

Motor torque

[Nm]

[6]

Motor power

[kW] or [hp]

[7]

Motor Rated

Voltage

[V]

[8]

DC-link voltage

[V]

[9]

Motor Thermal

Expressed as a percentage.

[10]

Drive thermal

Expressed as a percentage.

[11]

Heat sink temp.

Expressed as a percentage.

[12]

Analog input AI53

Expressed as a percentage.

[13]

Analog input AI54

Expressed as a percentage.

[14]

Analog input

AIFB10

[V]. AIFB10 is internal 10 V supply.

[15]

Analog input

AIS24V

[V] Analog input AICCT [17] [°]. AIS24V

is switch mode power supply: SMPS

24V.

[17]

Analog input

AICCT

[°]. AICCT is control card temperature.

[18]

Pulse input FI29

Expressed as a percentage.

[19]

Pulse input FI33

Expressed as a percentage.

[20]

Alarm number

The error number.

[21]

Warning number

[22]

Analog input x30

11

[23]

Analog input x30

12

[30]

Counter A

Number of counts

[31]

Counter B

Number of counts

[50]

FALSE

Enters the fixed value of false in the

comparator.

[51]

TRUE

Enters the fixed value of true in the

comparator.

[52]

Control ready

The control board receives supply

voltage

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

121

3

3