E-73 Terminal 29 Pulse Output Variable

Option:

Function:

[119] Torque % lim

E-76 Terminal X30/6 Pulse Output Variable

Select the variable for read-out on terminal X30/6.

This parameter is active when the General Purpose I/O Option

Module (OPCGPIO) is installed in the frequency converter.

Option:

Function:

[0]

*

No operation

[45]

Bus ctrl.

[48]

Bus ctrl., timeout

[100]

Output frequency

[101]

Reference

[102]

Feedback

[103]

Motor Current

[104]

Torque rel to limit

[105]

Torq relate to rated

[106]

Power

[107]

Speed

[108]

Torque

[109]

Max Out Freq

[119]

Torque % lim

E-78 Pulse Output Max Freq #X30/6

Range:

Function:

5000 Hz

*

[0 - 32000 Hz]

3.4.6 E-8# 24 V Encoder Input

Parameters to configure the Encoder outputs.

E-80 Term 32/33 Pulses Per Revolution

Range:

Function:

1024

*

[1 - 4096] Set the encoder pulses per revolution on the

motor shaft. Read the correct value from the

encoder.

E-81 Term 32/33 Encoder Direction

Option:

Function:

NOTE

This parameter cannot be adjusted
while the motor is running.

Change the detected encoder rotation

direction without changing the wiring to

the encoder.

[0]

*

Clockwise

Sets channel A 90° (electrical degrees)

behind channel B upon clockwise rotation

of the encoder shaft.

[1]

Counter

clockwise

Sets channel A 90° (electrical degrees)

ahead of channel B upon clockwise rotation

of the encoder shaft.

3.4.7 E-9# Bus Controlled

Parameters to configure digital, relay and pulse train
outputs to be controlled by the serial communications.

E-90 Digital & Relay Bus Control

Range:

Function:

0

*

[0 - 2147483647] This parameter holds the state of the

digital outputs and relays that is

controlled by bus.

A logical '1' indicates that the output is

high or active.

A logical '0' indicates that the output is

low or inactive.

Bit 0

Digital Output Terminal 27

Bit 1

Digital Output Terminal 29

Bit 2

Digital Output Terminal X 30/6

Bit 3

Digital Output Terminal X 30/7

Bit 4

Relay 1 output terminal

Bit 5

Relay 2 output terminal

Bit 6

Option B Relay 1 output terminal

Bit 7

Option B Relay 2 output terminal

Bit 8

Option B Relay 3 output terminal

Bit 9-31

Reserved for future terminals

Table 3.11

E-93 Pulse Out #27 Bus Control

Range:

Function:

0 %

*

[0 - 100 %] Set the output frequency transferred to the

output terminal 27 when the terminal is

configured as [45] Bus Controlled in

E-70 Terminal 27 Pulse Output Variable.

E-94 Pulse Out #27 Timeout Preset

Range:

Function:

0 %

*

[0 - 100 %] Set the output frequency transferred to the

output terminal 27 when the terminal is

configured as [48] Bus Ctrl Timeout in

E-70 Terminal 27 Pulse Output Variable and a

time-out is detected.

E-95 Pulse Out #29 Bus Control

Range:

Function:

0 %

*

[0 - 100 %] Set the output frequency transferred to the

output terminal 29 when the terminal is

configured as [45] Bus Controlled in

E-73 Terminal 29 Pulse Output Variable.

E-96 Pulse Out #29 Timeout Preset

Range:

Function:

0 %

*

[0 - 100 %] Set the output frequency transferred to the

output terminal 29 when the terminal is

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

51