Min. current at low speed is, H-70 warning current low, H-71 warning current high – GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 68: H-70 warning, Current low, H-71 warning current, High, 6 h-7# adjustable warnings

Advertising
background image

H-61 High Speed Load Compensation

Range:

Function:

100 %

*

[0 - 300

%]

Enter the % value to compensate voltage in

relation to load when the motor is running

at high speed and obtain the optimum U/f

characteristic. The motor size determines

the frequency range within which this

parameter is active.

Motor size

Change-over

0.25 kW - 7.5 kW

> 10 Hz

Table 3.14

H-64 Resonance Dampening

Range:

Function:

100 %

*

[0 - 500

%]

Enter the resonance dampening value. Set

H-64 Resonance Dampening and

H-65 Resonance Dampening Time Constant to

help eliminate high-frequency resonance

problems. To reduce resonance oscillation,

increase the value of H-64 Resonance

Dampening.

NOTE

H-64 Resonance Dampening will not have effect when
P-20 Motor Construction = [1] PM, non salient SPM.

H-65 Resonance Dampening Time Constant

Range:

Function:

5 ms

*

[5 - 50 ms] Set H-64 Resonance Dampening and

H-65 Resonance Dampening Time Constant to

help eliminate high-frequency resonance

problems. Enter the time constant that

provides the best dampening.

NOTE

H-65 Resonance Dampening Time Constant will not have
effect when P-20 Motor Construction = [1] PM, non salient
SPM.

H-66 Min. Current at Low Speed

Range:

Function:

100

%

*

[1 -

200 %]

Enter the minimum motor current at low speed,

see H-53 Model Shift Frequency. Increasing this

current improves motor torque at low speed.

H-66 Min. Current at Low Speed is enabled when

H-40 Configuration Mode [0] Speed open loop only.

The frequency converter runs with constant

current through motor for speeds below 10 Hz.

For speeds above 10 Hz, the motor flux model in

the frequency converter controls the motor.

F-40 Torque Limiter (Driving) and/or F-41 Torque

Limiter (Braking) automatically adjust H-66 Min.

Current at Low Speed. The parameter with the

H-66 Min. Current at Low Speed

Range:

Function:

highest value adjusts H-66 Min. Current at Low

Speed. The current setting in H-66 Min. Current at

Low Speed is composed of the torque generating

current and the magnetizing current.

Example: Set F-40 Torque Limiter (Driving) to 100%

and set F-41 Torque Limiter (Braking) to 60%.

H-66 Min. Current at Low Speed automatically

adjusts to about 127%, depending on the motor

size.

3.7.6 H-7# Adjustable Warnings

Parameters to configure the warnings limits for current,
speed, reference, and feedback.

Warnings are shown on the keypad, and can be
programmed to be outputs or to be read out via serial bus
in the Extended Status Word.

Illustration 3.31 Adjustable Warnings

H-70 Warning Current Low

Range:

Function:

0 A

*

[0 - par.

H-71 A]

Enter the I

LOW

value. When the motor current

falls below this limit, the display reads Current

Low. The signal outputs can be programmed

to produce a status signal on terminal 27 or

29 and on relay output 01 or 02. Refer to

Illustration 3.31.

H-71 Warning Current High

Range:

Function:

par.

DR-37 A

*

[par. H-70

- par. DR-37

A]

Enter the I

HIGH

value. When the motor

current exceeds this limit, the display

reads Current High. The signal outputs

can be programmed to produce a status

signal on terminal 27 or 29 and on relay

output 01 or 02. Refer to Illustration 3.31.

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

67

3

3