3.9.5 SP-5# Environment

Parameters to enable/disable the optional factory installed
A1/B1 RFI Filter, and Fan Monitor and to configure an
output filter if installed.

SP-50 RFI Filter

Option:

Function:

[0]

Off

Select [0] Off if the frequency converter is fed by an

isolated mains source (IT mains).

If a filter is used, select [0] Off during charging to

prevent a high leakage current making the RCD

switch.

In this mode, the internal RFI filter capacitors between

chassis and the mains RFI filter circuit are cut-out to

reduce the ground capacity currents.

[1]

*

On

Select [1] On to ensure that the frequency converter

complies with EMC standards.

13

0BB9

08.1

0

Illustration 3.40 RFI Filter

SP-51 DC Link Compensation

Option:

Function:

The rectified AC-DC voltage at the frequency

converter's DC link is associated with voltage ripples.

These ripples can increase in magnitude with

increased load. These ripples are undesirable because

they can generate current and torque ripples. A

compensation method is used to reduce these voltage

ripples at DC link. In general, DC link compensation is

recommended for most applications, but care must be

taken when operating in field weakening as it can

generate speed oscillations at the motor shaft. In field

weakening, it is recommended to turn DC link

compensation off.

[0]

*

Off

Select [0] Off to disable DC Link Compensation. this

disables compensation for ripple in the DC bus and

may be set when harmonic filters are used with the

drive.

[1]

On

Select [1] On to enable DC Link Compensation. This

function compensates for lower or higher DC bus

voltages to recreate a more perfect sine wave. May

overcompensate when harmonic filters are used.

SP-52 Fan Operation

Select minimum speed of the main fan.

Option:

Function:

[0]

*

Auto

Select [0] Auto to run fan only when internal

temperature in frequency converter is in range

35

°C to approx. 55 °C.

Fan will run at low speed below 35

°C, and at

full speed at approx. 55

°C.

[1]

On 50%

The fan will always run at 50% speed or above.

The fan will run at 50% speed at 35

°C, and at

full speed at approx. 55

°C.

[2]

On 75%

The fan will always run at 75% speed or above.

The fan will run at 75% speed at 35

°C, and at

full speed at approx. 55

°C.

[3]

On 100% The fan will run at 100% speed always.

[4]

Auto

(Low

temp

env.)

This selection is the same as [0] Auto but with

special considerations around and below 0

°C. In

selection [0] Auto there is a risk that the fan will

start running around 0

°C as the frequency

converter will fear a sensor fault and thus

protect the frequency converter while reporting

warning 66 "Heatsink Temperature Low".

Selection [4] Auto (Low temp env.) can be used in

very cold environments and prevent the

negative effects of this further cooling and avoid

warning 66.

SP-53 Fan Monitor

Option:

Function:

Select which reaction the frequency converter

should take in case a fan fault is detected.

[0]

Disabled

[1]

*

Warning

[2]

Trip

SP-55 Output Filter

Option:

Function:

NOTE

This parameter cannot be adjusted while
motor is running.

Select if a Sine-Wave output filter connected.

[0]

*

No

Filter

This is the default setting and should be used with

dU/dt filters or high-frequency common-mode (HF-

CM) filters.

[1]

Sine-

Wave

Filter

This setting is only for backwards compatibility. It

enables operation with FLUX control principle

when the parameters SP-56 Capacitance Output

Filter and SP-57 Inductance Output Filter are

programmed with the output filter capacitance

and inductance. It DOES NOT limit the range of

the switching frequency.

Parameter Descriptions

AF-650 GP Programming Guide

82