3.18.5 DR-6# Inputs/Outputs

Parameters to view the digital and analog I/O status
values.

DR-60 Digital Input

Range:

Function:

0

*

[0 -

1023]

View the signal states from the active digital inputs.

Example: Input 18 corresponds to bit no. 5, ‘0’ = no

signal, ‘1’ = connected signal.

Bit 0

Digital input term. 33

Bit 1

Digital input term. 32

Bit 2

Digital input term. 29

Bit 3

Digital input term. 27

Bit 4

Digital input term. 19

Bit 5

Digital input term. 18

Bit 6

Digital input term. 37

Bit 7

Digital input GP I/O term. X30/4

(OPCGPIO)

Bit 8

Digital input GP I/O term. X30/3

(OPCGPIO)

Bit 9

Digital input GP I/O term. X30/2

(OPCGPIO)

Bit 10-63

Reserved for future terminals

Table 3.30 Active Digital Inputs

Illustration 3.41 Relay Settings

DR-61 Terminal 53 Switch Setting

Option:

Function:

View the setting of input terminal 53.

[0]

*

Current

[1]

Voltage

[2]

Pt 1000 [°C]

[3]

Pt 1000 [°F]

[4]

Ni 1000 [°C]

[5]

Ni 1000 [°F]

DR-62 Analog Input 53

Range:

Function:

0

*

[-20 - 20]

View the actual value at input 53.

DR-63 Terminal 54 Switch Setting

Option:

Function:

View the setting of input terminal 54.

[0]

*

Current

[1]

Voltage

[2]

Pt 1000 [°C]

[3]

Pt 1000 [°F]

[4]

Ni 1000 [°C]

[5]

Ni 1000 [°F]

DR-64 Analog Input 54

Range:

Function:

0

*

[-20 - 20]

View the actual value at input 54.

DR-65 Analog Output 42 [mA]

Range:

Function:

0

*

[0 - 30] View the actual value at output 42 in mA. The

value shown reflects the selection in

AN-50 Terminal 42 Output.

DR-66 Digital Output [bin]

Range:

Function:

0

*

[0 - 15]

View the binary value of all digital outputs.

DR-67 Freq. Input #29 [Hz]

Range:

Function:

0

*

[0 - 130000] View the actual frequency rate on terminal 29.

DR-68 Freq. Input #33 [Hz]

Range:

Function:

0

*

[0 - 130000] View the actual value of the frequency applied

at terminal 33 as an impulse input.

DR-69 Pulse Output #27 [Hz]

Range:

Function:

0

*

[0 - 40000] View the actual value of pulses applied to

terminal 27 in digital output mode.

DR-70 Pulse Output #29 [Hz]

Range:

Function:

0

*

[0 - 40000] View the actual value of pulses at terminal 29 in

digital output mode.

DR-71 Relay Output [bin]

Range:

Function:

0

*

[0 - 511]

View the settings of all relays.

Illustration 3.43 Relay Settings

Parameter Descriptions

AF-650 GP Programming Guide

116