3.3 F-## Parameter Data Set

Parameter group related to the fundamental functions of
the drive.

3.3.1 F-0# Fundamental 0

Parameters to configure frequency command, base speed
settings, Torque Boost, and accel/decel time.

F-01 Frequency Setting 1

Option:

Function:

Select the reference input to be used

for the first reference signal.

F-01 Frequency Setting 1,

C-30 Frequency Command 2 and

C-34 Frequency Command 3 define

up to three different reference

signals. The sum of these reference

signals defines the actual reference.

[0]

No function

[1]

*

Analog Input 53

[2]

Analog Input 54

[7]

Frequency input 29

[8]

Frequency input 33

[11]

Local bus reference

[20]

Digital Potentiometer

[21]

Analog input X30-11

(General Purpose I/O Option Module)

[22]

Analog input X30-12

(General Purpose I/O Option Module)

F-02 Operation Method

Option:

Function:

Select which reference site to activate.

[0]

*

Linked to

Hand / Auto

Use local reference when in Hand mode; or

remote reference when in Auto mode.

[1]

Remote

Use remote reference in both Hand mode

and Auto mode.

[2]

Local

Use local reference in both Hand mode and

Auto mode.

NOTE

When set to [2] Local, the frequency
converter will start with this setting
again following a 'power down'.

F-03 Max Output Frequency 1

Range:

Function:

132

Hz

*

[1 -

590 Hz]

NOTE

This parameter cannot be adjusted while
the motor is running.

F-03 Max Output Frequency 1

Range:

Function:

NOTE

Max. output frequency cannot exceed
10% of the carrier frequency (F-26 Motor
Noise (Carrier Freq)
).

Provides a final limit on the output frequency

for improved safety in applications where you

want to avoid accidental over-speeding. This

limit is final in all configurations (independent

of the setting in H-40 Configuration Mode).

F-04 Base Frequency

Range:

Function:

60

Hz

*

[20 -

1000

Hz]

Min - Max motor frequency: 20-1000 Hz.

Select the motor frequency value from the

motor nameplate data. If a value different from

50 Hz or 60 Hz is selected, it is necessary to

adapt the load independent settings in

H-50 Motor Magnetisation at Zero Speed to

H-53 Model Shift Frequency. For 87 Hz operation

with 230/400 V motors, set the nameplate data

for 230 V/50 Hz. Adapt F-17 Motor Speed High

Limit [RPM] and F-53 Maximum Reference to the

87 Hz application.

F-05 Motor Rated Voltage

Range:

Function:

460 V

*

[10 - 1000 V] Enter the nominal motor voltage

according to the motor nameplate data.

The default value corresponds to the

nominal rated output of the unit.

F-07 Accel Time 1

Range:

Function:

3.00

s

*

[0.01 -

3600 s]

Enter the accel time, i.e. the acceleration time

from 0 RPM to the synchronous motor speed n

S

.

Choose a accel time such that the output

current does not exceed the current limit in

F-43 Current Limit during ramping. The value

0.00 corresponds to 0.01 s in speed mode. See

decel time in F-08 Decel Time 1.

Par

.

F

− 07 =

tacc

s

x

ns

RPM

ref

RPM

F-08 Decel Time 1

Range:

Function:

3.00

s

*

[0.01

- 3600

s]

Enter the decel time, that is, the deceleration

time from the synchronous motor speed n

s

to 0

RPM. Choose a decel time such that no over-

voltage arises in the inverter due to regenerative

operation of the motor, and such that the

generated current does not exceed the current

limit set in F-43 Current Limit. The value 0.00

Parameter Descriptions

AF-650 GP Programming Guide

32

DET-618C