E-10 accel, Time 2, 10 accel time 2 – GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 46: 2 e-1# additional accel/decel ramps

Advertising
background image

[36] Mains failure

inverse

Activates SP-10 Line failure. Mains failure

inverse is active in the Logic .0. situation.

[41] Latched Precise

Stop inverse

Sends a latched stop signal when the

precise stop function is activated in

H-83 Precise Stop Function. The Latched

Precise stop inverse function is available

for terminals 18 or 19.

[55] DigiPot

Increase

INCREASE signal to the Digital Potenti-

ometer function described in parameter

group F-9#

[56] DigiPot

Decrease

DECREASE signal to the Digital Potenti-

ometer function described in parameter

group F-9#

[57] DigiPot Clear

Clears the Digital Potentiometer reference

described in parameter group F-9#

[60] Counter A

(Terminal 29 or 33 only) Input for

increment counting in the LC counter.

[61] Counter A

(Terminal 29 or 33 only) Input for

decrement counting in the LC counter.

[62] Reset Counter

A

Input for reset of counter A.

[63] Counter B

(Terminal 29 or 33 only) Input for

increment counting in the LC counter.

[64] Counter B

(Terminal 29 or 33 only) Input for

decrement counting in the LC counter.

[65] Reset Counter

B

Input for reset of counter B.

[70] Mech. Brake

Feedback

Brake feedback for hoisting applications

[71] Mech. Brake

Feedback inv.

Inverted brake feedback for hoisting

applications

[80] PTC Card 1

All Digital Inputs can be set to PTC Card 1

[80]. However, only one Digital Input must

be set to this choice.

E-00 Digital I/O Mode

Option:

Function:

Digital inputs and programmed digital outputs are

pre-programmable for operation either in PNP or NPN

systems.

[0]

*

PNP Action on positive directional pulses

(↕). PNP systems

are pulled down to GND.

[1]

NPN Action on negative directional pulses

(↕). NPN

systems are pulled up to + 24 V, internally in the

frequency converter.

NOTE

Once this parameter has been changed, it must be
activated by performing a power cycle.

E-01 Terminal 18 Digital Input

Option: Function:

The options are the same as those listed for parameter

group E-0#.

E-02 Terminal 19 Digital Input

Option: Function:

The options are the same as those listed for parameter

group E-0#.

E-03 Terminal 27 Digital Input

Option: Function:

The options are the same as those listed for parameter

group E-0#.

E-04 Terminal 29 Digital Input

Option: Function:

The options are the same as those listed for parameter

group E-0#.

E-05 Terminal 32 Digital Input

Option: Function:

The options are the same as those listed for parameter

group E-0#.

E-06 Terminal 33 Digital Input

Option: Function:

The options are the same as those listed for parameter

group E-0#.

E-07 Terminal 37 Safe Stop

Option:

Function:

[1]

*

Safe Stop

Alarm

Coasts frequency converter when safe

stop is activated. Manual reset from

keypad, digital input or Network.

[3]

Safe Stop

Warning

Coasts frequency converter when safe

stop is activated (term 37 off). When safe

stop circuit is reestablished, the frequency

converter will continue without manual

reset.

NOTE

When Auto Reset/ Warning is selected the frequency
converter opens up for automatic restart.

Function

No.

PTC

Relay

Safe Stop

Alarm

[1]*

-

Safe Stop [A68]

Safe Stop

Warning

[3]

-

Safe Stop [W68]

Table 3.10 Overview of Functions, Alarms and Warnings

3.4.2 E-1# Additional Accel/Decel Ramps

Parameters to configure the Accel/Decel Ramps 2, 3, and 4.

E-10 Accel Time 2

Range:

Function:

3.00

s

*

[0.01 -

3600 s]

Enter the accel time from 0 RPM to the rated

motor speed n

s

. Choose a accel time such that

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

45

3

3