GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 165

Advertising
background image

No.

Description

Warning

Alarm/Trip

Alarm/Trip Lock

Parameter

Reference

64

Voltage Limit

X

65

Control Board Over-temperature

X

X

X

66

Heat sink Temperature Low

X

67

Option Module Configuration has Changed

X

69

Pwr. Card Temp

X

X

70

Illegal Drive configuration

X

75

Illegal Profile Sel.

X

76

Power Unit Setup

X

77

Reduced power mode

X

SP-59 Actual Number of

Inverter Units

78

Tracking Error

(X)

(X)

H-24 Tracking Error

Function

79

Illegal PS config

X

X

80

Drive Restored to Factory Settings

X

81

CSIV corrupt

X

82

CSIV parameter error

X

83

Illegal Option Combination

X

88

Option Detection

X

91

Analog input 54 wrong settings

X

S202

246

Pwr.card supply

250

New spare parts

X

251

New Type Code

X

X

Table 5.1 Alarm/Warning Code List

(X) Dependent on parameter

1) Cannot be Auto reset via H-04 Auto-Reset (Times)

A trip is the action following an alarm. The trip coasts the
motor and is reset by pressing [Reset] or by a digital input
(parameter group E-1# [1]). The origin event that caused
an alarm cannot damage the frequency converter or cause
dangerous conditions. A trip lock is an action when an
alarm occurs, which could damage the frequency converter

or connected parts. A trip lock situation can only be reset
by a power cycling.

Warning

yellow

Alarm

flashing red

Trip locked

yellow and red

Table 5.2 LED Indication

Bit

Hex

Dec

Alarm Word

Alarm Word 2

Warning Word

Warning
Word 2

Extended
Status Word

Alarm Word Extended Status Word

0

00000001

1

Brake Check (A28) ServiceTrip,

Read/Write

Brake Check (W28)

reserved

Ramping

1

00000002

2

Pwr. Card Temp

(A69)

ServiceTrip,

(reserved)

Pwr. Card Temp (W69)

reserved

Auto Tune Running

2

00000004

4

Earth Fault (A14)

ServiceTrip,

Typecode/

Sparepart

Earth Fault (W14)

reserved

Start CW/CCW

3

00000008

8

Ctrl.Card Temp

(A65)

ServiceTrip,

(reserved)

Ctrl.Card Temp (W65)

reserved

Slow Down

4

00000010

16

Ctrl. Word TO

(A17)

ServiceTrip,

(reserved)

Ctrl. Word TO (W17)

Catch Up

5

00000020

32

Over Current

(A13)

reserved

Over Current (W13)

reserved

Feedback High

6

00000040

64

Torque Limit

(A12)

reserved

Torque Limit (W12)

reserved

Feedback Low

Troubleshooting

AF-650 GP Programming Guide

164

DET-618C

5

5