3.11 DN-## DeviceNet Fieldbus

Parameter group related to Field Installed DeviceNet
Network Communications Option Module.

3.11.1 DN-0# Common Settings

Parameters to configure the commom settings for
DeviceNet.

DN-00 DeviceNet Protocol

Option:

Function:

[1]

*

DeviceNet

View the active CAN protocol.

NOTE

The options depend on installed option.

DN-01 Baud Rate Select

Select the network transmission speed. The selection must

correspond to the transmission speed of the master and the

other network nodes.

Option:

Function:

[16]

10 Kbps

[17]

20 Kbps

[18]

50 Kbps

[19]

100 Kbps

[20]

*

125 Kbps

[21]

250 Kbps

[22]

500 Kbps

DN-02 MAC ID

Range:

Function:

63

*

[0 - 63] Selection of station address. Every station

connected to the same network must have an

unambiguous address.

DN-05 Readout Transmit Error Counter

Range:

Function:

0

*

[0 - 255] View the number of CAN control transmission

errors since the last power-up.

DN-06 Readout Receive Error Counter

Range:

Function:

0

*

[0 - 255] View the number of CAN control receipt errors

since the last power-up.

DN-07 Readout Bus Off Counter

Range:

Function:

0

*

[0 - 255] View the number of Bus Off events since the last

power-up.

3.11.2 DN-1# DeviceNet

Parameters to configure the Process Data Type, Config
Write, Config Read, Warnings, and keypad control of
DeviceNet.

DN-10 Process Data Type Selection

Option:

Function:

Select the Instance (message) for data

transmission. The Instances available are

dependent upon the setting of O-10 Control

Word Profile.

When O-10 Control Word Profile is set to [0]

[0] Drive protocol, DN-10 Process Data Type

Selection options [0] INSTANCE 100/150 and

[1] INSTANCE 101/151 are available.

When O-10 Control Word Profile is set to [5]

ODVA, DN-10 Process Data Type Selection

options [2] INSTANCE 20/70 and [3] INSTANCE

21/71 are available.

Instances 100/150 and 101/151 are GE-

specific. Instances 20/70 and 21/71 are

ODVA-specific AC Drive profiles.

For guidelines in message selection, refer to

the DeviceNet Operating Instructions.

NOTE

A change to this parameter will be
executed immediately.

[0]

*

INSTANCE

100/150

[1]

INSTANCE

101/151

[2]

INSTANCE

20/70

[3]

INSTANCE

21/71

DN-11 Process Data Config Write

Select the process write data for I/O Assembly Instances 101/151.

Elements [2] and [3] of this array can be selected. Elements [0]

and [1] of the array are fixed.

Option:

Function:

[0]

*

None

[7]

Accel Time 1

[8]

Decel Time 1

[15]

Motor Speed High Limit [Hz]

[16]

Motor Speed Low Limit [Hz]

[17]

Motor Speed High Limit [RPM]

[18]

Motor Speed Low Limit [RPM]

[40]

Torque Limiter (Driving)

[41]

Torque Limiter (Braking)

[52]

Minimum Reference

[53]

Maximum Reference

[62]

Catch up/slow Down Value

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

93

3