GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 130

Advertising
background image

B-10 Brake Function

Option:

Function:

that AC brake is not as effective as dynamic

breaking with resistor.

AC brake is for Adv. Vector Control and flux

mode in both open and closed loop.

B-11 Brake Resistor (ohm)

Range:

Function:

50.00

Ohm

*

[5.00 -

65535.00

Ohm]

Set the brake resistor value in Ohms.

This value is used for monitoring the

power to the brake resistor in

B-13 Braking Thermal Overload. This

parameter is only active in frequency

converters with an integral dynamic

brake.

Use this parameter for values without

decimals. For a selection with two

decimals, use B-11 Brake Resistor (ohm).

B-12 Brake Power Limit (kW)

Range:

Function:

5.000

kW

*

[0.001 -

2000.000

kW]

B-12 Brake Power Limit (kW) is the expected

average power dissipated in the brake

resistor over a period of 120 s. It is used as

the monitoring limit for DR-33 Brake Energy /2

min and thereby specifies when a warning/

alarm is to be given.

To calculate B-12 Brake Power Limit (kW), the

following formula can be used.

P

br,avg

W

=

U

br

2

V

×

t

br

s

R

br

×

T

br

s

P

br,avg

is the average power dissipated in the

brake resistor, R

br

is the resistance of the

brake resistor. t

br

is the active breaking time

within the 120 s period, T

br

.

U

br

is the DC voltage where the brake

resistor is active. This depends on the unit as

follows:

200-240 V: 390 V

380-480 V: 778 V

525-600 V: 943 V

525-690 V: 1099 V

NOTE

If R

br

is not known or if T

br

is different

from 120 s, the practical approach is to
run the brake application, readout
DR-33 Brake Energy /2 min and then
enter this + 20% in B-12 Brake Power
Limit (kW)
.

B-13 Braking Thermal Overload

Option:

Function:

This parameter is only active in frequency

converters with an integral dynamic brake.

This parameter enables monitoring of the

power to the brake resistor. The power is

calculated on the basis of the resistance

(B-11 Brake Resistor (ohm)), the DC link voltage,

and the resistor duty time.

[0]

*

Off

No brake power monitoring required.

[1]

Warning

Activates a warning on the display when the

power transmitted over 120 s exceeds 100% of

the monitoring limit (B-12 Brake Power Limit

(kW) .

The warning disappears when the transmitted

power falls below 80% of the monitoring limit.

[2]

Trip

Trips frequency converter and displays an

alarm when the calculated power exceeds

100% of the monitoring limit.

[3]

Warning

and trip

Activates both of the above, including

warning, trip and alarm.

If power monitoring is set to [0] Off or [1] Warning, the
brake function remains active, even if the monitoring limit
is exceeded. This may lead to thermal overload of the
resistor. It is also possible to generate a warning via a
relay/digital outputs. The measuring accuracy of the power
monitoring depends on the accuracy of the resistance of
the resistor (better than

±20%).

B-15 Brake Check

Option:

Function:

Select type of test and monitoring function to

check the connection to the brake resistor, or

whether a brake resistor is present, and then

display a warning or an alarm in the event of a

fault.

NOTE

The brake resistor disconnection function is
tested during power-up. However the brake
IGBT test is performed when there is no
braking. A warning or trip disconnects the
brake function.

The testing sequence is as follows:

1.

The DC link ripple amplitude is

measured for 300 ms without braking.

2.

The DC link ripple amplitude is

measured for 300 ms with the brake

turned on.

3.

If the DC link ripple amplitude while

braking is lower than the DC link ripple

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

129

3

3

Advertising