Logic controller action, Lc-52 logic controller action ), Logic controller action ) – GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 127: Lc-43 logic rule operator 2 , a, 5 lc-5# states

Advertising
background image

LC-43 Logic Rule Operator 2

Array [6]

Option:

Function:

Select the second logical operator to be

used on the boolean input calculated in

LC-40 Logic Rule Boolean 1, LC-41 Logic Rule

Operator 1, and LC-42 Logic Rule Boolean 2,

and the boolean input coming from

LC-42 Logic Rule Boolean 2.

[LC-44] signifies the boolean input of

LC-44 Logic Rule Boolean 3.

[LC-40/LC-42] signifies the boolean input

calculated in LC-40 Logic Rule Boolean 1,

LC-41 Logic Rule Operator 1, and LC-42 Logic

Rule Boolean 2. [0] DISABLED (factory

setting). select this option to ignore

LC-44 Logic Rule Boolean 3.

[0]

*

DISABLED

[1]

AND

[2]

OR

[3]

AND NOT

[4]

OR NOT

[5]

NOT AND

[6]

NOT OR

[7]

NOT AND NOT

[8]

NOT OR NOT

LC-44 Logic Rule Boolean 3

Array [6]

Option:

Function:

[0]

*

False Select the third boolean (TRUE or FALSE) input for

the selected logic rule. See LC-01 Start Event ([0] -

[61]) and LC-02 Stop Event ([70] - [75]) for further

description.

3.19.5 LC-5# States

Parameters to configure the Logic Controller (LC) states.
States define the events and actions to take place in the
drive.

LC-51 Logic Controller Event

Array [20]

Option:

Function:

[0]

*

False Select the boolean input (TRUE or FALSE) to define

the Logic Controller event.See LC-01 Start Event ([0] -

[61]) and LC-02 Stop Event ([70] - [74]) for further

description.

LC-52 Logic Controller Action

Array [20]

Option:

Function:

[0]

*

DISABLED

Select the action corresponding to the LC

event. Actions are executed when the

corresponding event (defined in

LC-52 Logic Controller Action

Array [20]

Option:

Function:

LC-51 Logic Controller Event) is evaluated

as true. The following actions are

available for selection:

[0] *DISABLED

[1]

No action

[2]

Select set-up 1

Changes the active set-up (K-10 Active

Set-up) to ‘1’.

If the set-up is changed, it will merge

with other set-up commands coming

from either the digital inputs or via a

Network.

[3]

Select set-up 2

Changes the active set-up K-10 Active Set-

up) to ‘2’.

If the set-up is changed, it will merge

with other set-up commands coming

from either the digital inputs or via a

Network.

[4]

Select set-up 3

Changes the active set-up (K-10 Active

Set-up) to ‘3’.

If the set-up is changed, it will merge

with other set-up commands coming

from either the digital inputs or via a

Network.

[5]

Select set-up 4

Changes the active set-up (K-10 Active

Set-up) to ‘4’.

If the set-up is changed, it will merge

with other set-up commands coming

from either the digital inputs or via a

Network.

[10]

Select preset ref

0

Selects preset reference 0.

If the active preset reference is changed,

it will merge with other preset reference

commands coming from either the digital

inputs or via a Network.

[11]

Select preset ref

1

Selects preset reference 1.

If the active preset reference is changed,

it will merge with other preset reference

commands coming from either the digital

inputs or via a Network.

[12]

Select preset ref

2

Selects preset reference 2.

If the active preset reference is changed,

it will merge with other preset reference

commands coming from either the digital

inputs or via a Network.

[13]

Select preset ref

3

Selects preset reference 3.

If the active preset reference is changed,

it will merge with other preset reference

commands coming from either the digital

inputs or via a Network.

Parameter Descriptions

AF-650 GP Programming Guide

126

DET-618C

3

3