3.18 DR-##

Data

Read-outs

Parameter group related to data readouts in the drive for
references, voltages, control, alarms, warnings, and status
words.

3.18.1 DR-0# General Status

Parameters to view the calculated references, the active
control word, and status word.

DR-00 Control Word

Range:

Function:

0

*

[0 - 65535] View the Control word sent from the frequency

converter via the serial communication port in

hex code.

DR-01 Reference [Unit]

Range:

Function:

0 ReferenceFeed-

backUnit

*

[-999999 - 999999

ReferenceFeed-

backUnit]

View the present

reference value applied

on impulse or analog

basis in the unit

resulting from the

configuration selected

in H-40 Configuration

Mode (Hz, Nm or RPM).

DR-02 Reference [%]

Range:

Function:

0 %

*

[-200 - 200

%]

View the total reference. The total

reference is the sum of digital, analog,

preset, bus, and freeze references, plus

catch-up and slow-down.

DR-03 Status Word

Range:

Function:

0

*

[0 - 65535] View the Status word sent from the frequency

converter via the serial communication port in

hex code.

DR-05 Main Actual Value [%]

Range:

Function:

0 %

*

[-100 - 100 %] View the two-byte word sent with the

Status word to the bus Master reporting

the Main Actual Value.

DR-09 Custom Readout

Range:

Function:

0 CustomRea-

doutUnit

*

[0 - 0 CustomRea-

doutUnit]

View the value of

custom readout from

K-30 Unit for Custom

Readout to K-32 Max

Value of Custom Readout

3.18.2 DR-1# Motor Status

Parameters to view the motor status values.

DR-10 Power [kW]

Range:

Function:

0 kW

*

[0 -

10000 kW]

Displays motor power in kW. The value

shown is calculated on the basis of the actual

motor voltage and motor current. The value

is filtered, and therefore approx. 30 ms may

pass from when an input value changes to

when the data read-out values change. The

resolution of read-out value on fieldbus is in

10 W steps.

DR-11 Power [hp]

Range:

Function:

0 hp

*

[0 - 10000

hp]

View the motor power in HP. The value

shown is calculated on the basis of the

actual motor voltage and motor current. The

value is filtered, and therefore approximately

30 ms may pass from when an input value

changes to when the data read-out values

change.

DR-12 Motor Voltage

Range:

Function:

0 V

*

[0 - 6000 V] View the motor voltage, a calculated value

used for controlling the motor.

DR-13 Frequency

Range:

Function:

0 Hz

*

[0 - 6500 Hz] View the motor frequency, without

resonance dampening.

DR-14 Motor current

Range:

Function:

0 A

*

[0 - 10000

A]

View the motor current measured as a mean

value, I

RMS

. The value is filtered, and thus

approximately 30 ms may pass from when

an input value changes to when the data

read-out values change.

DR-15 Frequency [%]

Range:

Function:

0 %

*

[-100 -

100 %]

View a two-byte word reporting the actual

motor frequency (without resonance

dampening) as a percentage (scale 0000-4000

Hex) of F-03 Max Output Frequency 1. Set

PB-16 PCD Read Configuration index 1 to send

it with the Status Word instead of the MAV.