AN-34 Term. X30/11 Low Ref./Feedb. Value

Range:

Function:

0

*

[-999999.999 -

999999.999]

Sets the analog input scaling value to

correspond to the low voltage value

(set in AN-30 Terminal X30/11 Low

Voltage).

AN-35 Term. X30/11 High Ref./Feedb. Value

Range:

Function:

100

*

[-999999.999 -

999999.999]

Sets the analog input scaling value

to correspond to the high voltage

value (set in AN-31 Terminal X30/11

High Voltage).

AN-36 Term. X30/11 Filter Time Constant

Range:

Function:

0.001 s

*

[0.001 - 10 s]

NOTE

This parameter cannot be adjusted
while the motor is running.

A 1

st

order digital low pass filter time

constant for suppressing electrical noise

on terminal X30/11.

3.8.5 AN-4# Analog Input X30/12

Parameters to configure the scaling and limits for Analog
Input 2 associated with OPCGPIO General Purpose Field
Installed Option Module.

AN-40 Terminal X30/12 Low Voltage

Range:

Function:

0.07 V

*

[0 - par. AN-41

V]

Sets the analog input scaling value to

correspond to the low reference/

feedback value set in AN-44 Term.

X30/12 Low Ref./Feedb. Value.

AN-41 Terminal X30/12 High Voltage

Range:

Function:

10 V

*

[par. AN-40 - 10

V]

Sets the analog input scaling value to

correspond to the high reference/

feedback value set in AN-45 Term.

X30/12 High Ref./Feedb. Value.

AN-44 Term. X30/12 Low Ref./Feedb. Value

Range:

Function:

0

*

[-999999.999 -

999999.999]

Sets the analog output scaling value

to correspond to the low voltage

value set in AN-40 Terminal X30/12

Low Voltage.

AN-45 Term. X30/12 High Ref./Feedb. Value

Range:

Function:

100

*

[-999999.999 -

999999.999]

Sets the analog input scaling value

to correspond to the high voltage

value set in AN-41 Terminal X30/12

High Voltage.

AN-46 Term. X30/12 Filter Time Constant

Range:

Function:

0.001 s

*

[0.001 - 10 s]

NOTE

This parameter cannot be adjusted
while the motor is running.

A 1

st

order digital low pass filter time

constant for suppressing electrical noise

on terminal X30/12.

3.8.6 AN-5# Analog Output 42

Parameters to configure the scaling and limits for Analog
Output 1 (terminal 42)

AN-50 Terminal 42 Output

Option:

Function:

Select the function of Terminal 42 as an

analog current output. Depending on the

selection the output is either a 0-20 mA or

4-20 mA output. The current value can be

read out in keypad in DR-65 Analog Output 42

[mA].

[0]

*

No

operation

When no signal on the analog output.

[100] Output

frequency

0 Hz = 0 mA; 100 Hz = 20 mA.

[101] Reference

F-50 Reference Range [Min - Max] 0% = 0 mA;

100% = 20 mA

F-50 Reference Range [-Max - Max] -100% = 0

mA; 0% = 10 mA; +100% = 20 mA

[102] Feedback

F-50 Reference Range [Min - Max] 0% = 0 mA;

100% = 20 mA

F-50 Reference Range [-Max - Max] -100% = 0

mA; 0% = 10 mA; +100% = 20 mA

[103] Motor

Current

0–20 mA is equal to the range of 0 A to

DR-37 Drive Max. Current (160% current) with

default scaling.

Example:

Inverter norm current (11 kW) = 24 A. 160%

=38.4 A. Motor Current = 22 A.

An analog output of 11.46 mA equals:

11.46 mA x 38.4A/20 mA = 22 A

In case 20 mA must be equal to a value

different than Imax e.g P-06 Base Speed Motor

Parameter Descriptions

AF-650 GP Programming Guide

74

DET-618C