E-63 Term. 29 High Ref./Feedb. Value

Range:

Function:

Select terminal 29 as a

digital input

(E-52 Terminal 29 Mode =

[0] input (default) and

E-04 Terminal 29 Digital

Input = applicable

value).

E-64 Pulse Filter Time Constant #29

Range:

Function:

100 ms

*

[1 - 1000

ms]

Enter the pulse filter time constant. The

pulse filter dampens oscillations of the

feedback signal, which is an advantage if

there is a lot of noise in the system. A

high time constant value results in better

dampening but also increases the time

delay through the filter.

E-65 Term. 33 Low Frequency

Range:

Function:

100 Hz

*

[0 - 110000

Hz]

Enter the low frequency

corresponding to the low motor shaft

speed (i.e. low reference value) in

E-67 Term. 33 Low Ref./Feedb. Value.

E-66 Term. 33 High Frequency

Range:

Function:

100 Hz

*

[0 - 110000

Hz]

Enter the high frequency

corresponding to the high motor shaft

speed (i.e. high reference value) in

E-68 Term. 33 High Ref./Feedb. Value.

E-67 Term. 33 Low Ref./Feedb. Value

Range:

Function:

0

*

[-999999.999 -

999999.999]

Enter the low reference value [RPM]

for the motor shaft speed. This is also

the low feedback value, see also

E-62 Term. 29 Low Ref./Feedb. Value.

E-68 Term. 33 High Ref./Feedb. Value

Range:

Function:

1500.000 Reference-

FeedbackUnit

*

[-999999.999 -

999999.999

ReferenceFeed-

backUnit]

Enter the high

reference value

[RPM] for the motor

shaft speed. See

also E-63 Term. 29

High Ref./Feedb.

Value.

E-69 Pulse Filter Time Constant #33

Range:

Function:

100 ms

*

[1 - 1000

ms]

Enter the pulse filter time constant. The

low-pass filter reduces the influence on

E-69 Pulse Filter Time Constant #33

Range:

Function:

and dampens oscillations on the feedback

signal from the control.

This is an advantage, e.g. if there is a

great amount on noise in the system.

3.4.5 E-7# Pulse Output

Parameters to configure terminal 27 and 29 as Pulse Train
Outputs and to configure Encoder input terminals 32 and
33.

E-70 Terminal 27 Pulse Output Variable

Option:

Function:

[0]

*

No operation

Select the desired display output for

terminal 27.

[45]

Bus ctrl.

[48]

Bus ctrl., timeout

[100] Output frequency

[101] Reference

[102] Feedback

[103] Motor Current

[104] Torque rel to limit

[105] Torq relate to rated

[106] Power

[107] Speed

[108] Torque

[109] Max Out Freq

[119] Torque % lim

E-72 Pulse Output Max Freq #27

Range:

Function:

5000 Hz

*

[0 - 32000 Hz] Set the maximum frequency for

terminal 27, corresponding to the

output variable selected in

E-70 Terminal 27 Pulse Output Variable.

E-73 Terminal 29 Pulse Output Variable

Option:

Function:

[0]

*

No operation

Select the desired display output for

terminal 29.

[45]

Bus ctrl.

[48]

Bus ctrl., timeout

[100] Output frequency

[101] Reference

[102] Feedback

[103] Motor Current

[104] Torque rel to limit

[105] Torq relate to rated

[106] Power

[107] Speed

[108] Torque

[109] Max Out Freq

Parameter Descriptions