F-68 Relative Scaling Reference Resource

Option:

Function:

Illustration 3.14 Resultant Actual Reference

[0]

*

No function

[1]

Analog Input

53

[2]

Analog Input

54

[7]

Frequency

input 29

[8]

Frequency

input 33

[11]

Local bus

reference

[20]

Digital

Potentiometer

[21]

Analog input

X30-11

[22]

Analog input

X30-12

3.3.9 F-9# Digital Potentiometer

Parameters to configure drive digital pot-meter function.

F-90 Step Size

Range:

Function:

0.10 %

*

[0.01 -

200 %]

Enter the increment size required for

INCREASE/DECREASE, as a percentage of

the synchronous motor speed, n

s

. If

INCREASE/DECREASE is activated the

resulting reference will be increased/

decreased by the amount set in this

parameter.

F-91 Accel/Decel Time

Range:

Function:

1 s

*

[0 -

3600 s]

Enter the ramp time, i.e. the time for adjustment

of the reference from 0% to 100% of the

specified digital potentiometer function (Increase,

Decrease or Clear).

If Increase/ Decrease is activated for longer than

the ramp delay period specified in F-95 Accel/

Decel Ramp Delay the actual reference will be

acceled/deceled according to this ramp time. The

ramp time is defined as the time used to adjust

the reference by the step size specified in

F-90 Step Size.

F-92 Power Restore

Option:

Function:

[0]

*

Off

Resets the Digital Pot-Meter reference to 0% after

power up.

[1]

On

Restores the most recent Digital Pot-Meter reference at

power up.

F-93 Maximum Limit

Range:

Function:

100 %

*

[-200 - 200

%]

Set the maximum permissible value for

the resultant reference. This is advisable if

the Digital Pot-Meter is used for fine

tuning of the resulting reference.

F-94 Minimum Limit

Range:

Function:

-100 %

*

[-200 - 200

%]

Set the minimum permissible value for

the resultant reference. This is advisable

if the Digital Pot-Meter is used for fine

tuning of the resulting reference.

F-95 Accel/Decel Ramp Delay

Range:

Function:

0

*

[0 - 0] Enter the delay required from activation of the

digital pot-meter function until the frequency

converter starts to ramp the reference. With a delay

of 0 ms, the reference starts to ramp as soon as

INCREASE/ DECREASE is activated. See also

F-91 Accel/Decel Time.

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

41