GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 45

Advertising
background image

Preset ref. bit

2

1

0

Preset ref. 0

0

0

0

Preset ref. 1

0

0

1

Preset ref. 2

0

1

0

Preset ref. 3

0

1

1

Preset ref. 4

1

0

0

Preset ref. 5

1

0

1

Preset ref. 6

1

1

0

Preset ref. 7

1

1

1

Table 3.7

[19] Freeze

ref

Freezes the actual reference, which is now the

point of enable/condition for Speed up and Speed

down to be used. If Speed up/down is used, the

speed change always follows ramp 2 (E-10 Accel

Time 2 and E-11 Decel Time 2) in the range 0 -

F-53 Maximum Reference.

[20] Freeze

output

Freezes the actual motor frequency (Hz), which is

now the point of enable/condition for Speed up

and Speed down to be used. If Speed up/down is

used, the speed change always follows ramp 2

(E-10 Accel Time 2 and E-11 Decel Time 2) in the

range 0 - F-04 Base Frequency.

NOTE

When Freeze output is active, the frequency
converter cannot be stopped via a low ‘start
[8]’ signal. Stop the frequency converter via a
terminal programmed for Coasting inverse [2]
or Coast and reset, inverse.

[21] Speed

up

Select Speed up and Speed down if digital control

of the up/down speed is desired (motor potenti-

ometer). Activate this function by selecting either

Freeze reference or Freeze output. When Speed

up/ down is activated for less than 400 msec. the

resulting reference will be increased/ decreased by

0.1 %. If Speed up/ down is activated for more

than 400 msec. the resulting reference will follow

the setting in accel/decel parameters.

Shut down

Catch up

Unchanged speed

0

0

Reduced by %-value

1

0

Increased by %-value

0

1

Reduced by %-value

1

1

Table 3.8

[22] Speed down

Same as Speed up [21].

[23] Set-up select

bit 0

Select Set-up select bit 0 or Select Set-up

select bit 1 to select one of the four set-ups.

Set K-10 Active Set-up to Multi Set-up.

[24] Set-up select

bit 1

Same as Set-up select bit 0 [23].

[26] Precise stop

inv.

Prolongs stop signal to give a precise stop

independent of speed.

Sends an inverted stop signal when the

precise stop function is activated in

H-83 Precise Stop Function.

Precise stop inverse function is available for

terminals 18 or 19.

[27] Precise start,

stop

Use when Precise ramp stop [0] is selected in

H-83 Precise Stop Function.

Illustration 3.15

[28] Catch up

Increases reference value by percentage

(relative) set in F-62 Catch up/slow Down

Value.

[29] Slow down

Reduces reference value by percentage

(relative) set in F-62 Catch up/slow Down

Value.

[30] Counter

input

Precise stop function in H-83 Precise Stop

Function acts as Counter stop or speed

compensated counter stop with or without

reset. The counter value must be set in

H-84 Precise Stop Counter Value.

[32] Pulse input

Use pulse sequence as either reference or

feedback. Scaling is done in parameter group

group E-6#.

[34] Ramp bit 0

Enables a choice between one of the 4 ramps

available, according to the table below.

[35] Ramp bit 1

Same as Ramp bit 0.

Preset ramp bit

1

0

Ramp 1

0

0

Ramp 2

0

1

Ramp 3

1

0

Ramp 4

1

1

Table 3.9

Parameter Descriptions

AF-650 GP Programming Guide

44

DET-618C