Option:

Function:

[0]

*

No copy

[1]

All to Keypad

Copies all parameters in all set-ups from the

frequency converter memory to the keypad

memory.

[2]

All from

Keypad

Copies all parameters in all set-ups from the

keypad memory to the frequency converter

memory.

[3]

Size indep.

From Keypad

Copy only the parameters that are

independent of the motor size. The latter

selection can be used to program several

frequency converters with the same function

without disturbing motor data.

K-51 Set-up Copy

Option:

Function:

[0]

*

No copy

No function

[1]

Copy to set-

up 1

Copies all parameters in the present

Programming Set-up (defined in K-11 Edit

Set-up) to Set-up 1.

[2]

Copy to set-

up 2

Copies all parameters in the present

Programming Set-up (defined in K-11 Edit

Set-up) to Set-up 2.

[3]

Copy to set-

up 3

Copies all parameters in the present

Programming Set-up (defined in K-11 Edit

Set-up) to Set-up 3.

[4]

Copy to set-

up 4

Copies all parameters in the present

Programming Set-up (defined in K-11 Edit

Set-up) to Set-up 4.

[9]

Copy to all

Copies the parameters in the present set-up

over to each of the set-ups 1 to 4.

3.2.7 K-6# Password Protection

Parameters for setting the Password Protection for the
drive parameters.

K-60 Main Menu Password

Range:

Function:

100

*

[-9999 -

9999]

Define the password for access to the Main

Menu via the [Main Menu] key. If K-61 Access

to Main Menu w/o Password is set to [0] Full

access, this parameter will be ignored.

K-61 Access to Main Menu w/o Password

Option:

Function:

[0]

*

Full access

Disables password defined in K-60 Main

Menu Password.

[1]

Keypad: Read only Prevent unauthorized editing of Main

Menu parameters.

K-61 Access to Main Menu w/o Password

Option:

Function:

[2]

Keypad: No access Prevent unauthorized viewing and

editing of Main Menu parameters.

[3]

Bus: Read only

[4]

Bus: No access

[5]

All: Read only

[6]

All: No access

If [0] Full access is selected then K-60 Main Menu Password,
K-65 Quick Menu Password and K-66 Access to Quick Menu
w/o Password
will be ignored.

K-65 Quick Menu Password

Range:

Function:

200

*

[-9999 -

9999]

Define the password for access to the Quick

Menu via the [Quick Menu] key. If

K-66 Access to Quick Menu w/o Password is

set to [0] Full access, this parameter will be

ignored.

K-66 Access to Quick Menu w/o Password

Option:

Function:

[0]

*

Full access

Disables the password defined in

K-65 Quick Menu Password.

[1]

Keypad: Read

only

Prevents unauthorised editing of Quick

Menu parameters.

[2]

Keypad: No

access

Prevents unauthorised viewing and

editing of Quick Menu parameters.

[3]

Bus: Read only

Read only functions for Quick Menu

parameters on Fieldbus and/ or Drive

standard bus.

[4]

Bus: No access

No access to Quick Menu parameters is

allowed via Fieldbus and/ or Drive

standard bus.

[5]

All: Read only

read only function for Quick Menu

parameters on keypad, Fieldbus or Drive

standard bus.

[6]

All: No access

No access from keypad, Fieldbus or Drive

standard bus is allowed.

If K-61 Access to Main Menu w/o Password is set to [0] Full
access
then this parameter will be ignored.

K-67 Bus Password Access

Range:

Function:

0

*

[0 - 9999] Writing to this parameter enables users to unlock

the frequency converter from network/DCT-10.

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

31