3.12 PB-##

Profibus

Parameter group related to Field Installed Profibus DP
Network Communications Option Module.

PB-00 Setpoint

Range:

Function:

0

*

[0 - 65535] This parameter receives cyclical reference from a

Master Class 2. If the control priority is set to

Master Class 2, the reference for the frequency

converter is taken from this parameter, whereas

the cyclical reference will be ignored.

PB-07 Actual Value

Range:

Function:

0

*

[0 - 65535] This parameter delivers the MAV for a Master

Class 2. The parameter is valid if the control

priority is set to Master Class 2.

PB-15 PCD Write Configuration

Array [10]

Option:

Function:

Select the parameters to

be assigned to PCD 3 to

10 of the messages. The

number of available PCDs

depends on the message

type. The values in PCD 3

to 10 will then be written

to the selected

parameters as data

values. Alternatively,

specify a standard

Profibus message in

PB-22 Telegram Selection.

[0]

*

None

[7]

Accel Time 1

[8]

Decel Time 1

[15]

Motor Speed High Limit [Hz]

[16]

Motor Speed Low Limit [Hz]

[17]

Motor Speed High Limit [RPM]

[18]

Motor Speed Low Limit [RPM]

[40]

Torque Limiter (Driving)

[41]

Torque Limiter (Braking)

[52]

Minimum Reference

[53]

Maximum Reference

[62]

Catch up/slow Down Value

[110]

Accel Time 2

[111]

Decel Time 2

[190]

Digital & Relay Bus Control

[193]

Pulse Out #27 Bus Control

[195]

Pulse Out #29 Bus Control

[197]

Pulse Out #X30/6 Bus Control

[222]

Jog Accel/Decel Time

[223]

Quick Stop Decel Time

PB-15 PCD Write Configuration

Array [10]

Option:

Function:

[653]

Terminal 42 Output Bus

Control

[663]

Terminal X30/8 Bus Control

[748]

PCD Feed Forward

[890]

Bus Jog 1 Speed

[891]

Bus Jog 2 Speed

[1280] Fieldbus CTW 1

[1282] Fieldbus REF 1

PB-16 PCD Read Configuration

[10] Array

Option:

Function:

Select the parameters to be

assigned to PCD 3 to 10 of

the messages. The number

of available PCDs depends

on the message type. PCDs

3 to 10 contain the actual

data values of the selected

parameters. For standard

Profibus messages, see

PB-22 Telegram Selection.

[0]

*

None

[515]

Readout: actual setup

[1200] Control Word

[1201] Reference [Unit]

[1202] Reference %

[1203] Status Word

[1205] Main Actual Value [%]

[1209] Custom Readout

[1210] Power [kW]

[1211] Power [hp]

[1212] Motor Voltage

[1213] Frequency

[1214] Motor current

[1215] Frequency [%]

[1216] Torque [Nm]

[1217] Speed [RPM]

[1218] Motor Thermal

[1219] KTY sensor temperature

[1220] Motor Angle

[1221] Torque [%] High Res.

[1222] Torque [%]

[1225] Torque [Nm] High

[1230] DC Link Voltage

[1232] Brake Energy /s

[1233] Brake Energy /2 min

[1234] Heatsink Temp.

[1235] Drive Thermal

[1238] Logic Controller State

[1239] Control Card Temp.