EN-37 COS Inhibit Timer

Range:

Function:

[0–65.535

ms]

Read only Change-Of-State inhibit timer. If the

option is configured for COS operation, this

inhibit timer can be configured in the Forward

Open telegram to prevent that continuously

changing PCD data generates extensive network

traffic. The inhibit time is in milliseconds,

0=disabled.

EN-38 COS Filters

Range:

Function:

[[0-9] Filter 0–9

(0000-FFFFhex)]

Change-Of-State PCD filters. Sets up a filter

mask for each word of process data when

operating in COS-mode. Single bits in the

PCD’s can be filtered in/out.

EN-40 Status Parameter

Range:

Function:

0

*

[0 - 0]

NOTE

This parameter is for Modbus TCP only

EN-41 Slave Message Count

Range:

Function:

0

*

[0 - 0]

NOTE

This parameter is for Modbus TCP only

EN-42 Slave Exception Message Count

Range:

Function:

0

*

[0 - 0]

NOTE

This parameter is for Modbus TCP only

EN-80 FTP Server

Option:

Function:

[0]

*

Disabled

Disables the built-in FTP server.

[1]

Enabled

Enables the built-in FTP server.

EN-81 HTTP Server

Option:

Function:

[0]

*

Disabled

[1]

Enabled

Enables the built-in HTTP (web) server.

EN-82 SMTP Service

Option:

Function:

[0]

*

Disabled

[1]

Enabled

Enables the SMTP (e-mail) service on the option.

EN-89 Transent Socket Channel Port

Range:

Function:

0

*

[0–9999] Configures the TCP port-number for the transent

socket channel. This enables Drive-messages to be

sent transently on Ethernet via TCP. Default value

is 4000, 0 means disabled.

EN-90 Cable Diagnostic

Option:

Function:

Enables/disables advanced Cable diagnosis

function. If enabled, the distance to cable errors

can be read out in EN-93 Cable Error Length. The

parameter resumes to the default setting of

Disable after the diagnostics have finished.

[0]

*

Disabled

[1]

Enabled

NOTE

The cable diagnostics function is only issued on ports
where there is no link (see EN-10 Link Status, Link Status)

EN-91 Auto Cross-Over

Option:

Function:

[0]

Disable

Disables the auto cross-over function.

[1]

*

Enable

Enables the auto cross-over function.

NOTE

Disabling of the auto cross-over function requires crossed
Ethernet cables for daisy-chaining the options.

EN-92 IGMP Snooping

Option:

Function:

This prevents flooding of the Ethernet protocol

stack by only forwarding multicast packets to ports

that are a member of the multicast group.

[0]

Disable Disables the IGMP snooping function.

[1]

*

Enable

Enables the IGMP snooping function.

EN-93 Cable Error Length

Range:

Function:

0

*

[0 -

65535]

If Cable Diagnostics is enabled in EN-90 Cable

Diagnostic, the built-in switch is possible via Time

Domain Reflectometry (TDR). This measurement

technique detects common cabling problems

such as open circuits, short circuits, and

impedance mismatches or breaks in transmission

cables. The distance from the option to the error

is displayed in meters with an accuracy of

±2 m.

The value 0 means that no errors detected.