P-33 Stator Leakage Reactance (X1)

Range:

Function:

3.

Use the X

1

default setting. The

frequency converter establishes

the setting on the basis of the

motor name plate data.

See Illustration 3.20.

NOTE

P-33 Stator Leakage Reactance (X1) will not have effect
when P-20 Motor Construction = [1] PM, non salient SPM.

P-34 Rotor Leakage Reactance (X2)

Range:

Function:

4.0000

Ohm

*

[0.0400 -

400.0000

Ohm]

Set the rotor leakage reactance of the

motor using one of these methods:

1.

Run an Auto Tune on a cold

motor. The frequency converter

will measure the value from the

motor.

2.

Enter the X

2

value manually.

Obtain the value from the motor

supplier.

3.

Use the X

2

default setting. The

frequency converter establishes

the setting on the basis of the

motor name plate data.

See Illustration 3.20.

NOTE

P-34 Rotor Leakage Reactance (X2) will not have effect when
P-20 Motor Construction = [1] PM, non salient SPM.

P-35 Main Reactance (Xh)

Range:

Function:

100.0000

Ohm

*

[1.0000 -

10000.0000

Ohm]

Set the main reactance of the motor

using one of these methods:

1.

Run an Auto Tune on a cold

motor. The frequency

converter will measure the

value from the motor.

2.

Enter the X

h

value manually.

Obtain the value from the

motor supplier.

3.

Use the X

h

default setting.

The frequency converter

establishes the setting on

the basis of the motor name

plate data.

P-36 Iron Loss Resistance (Rfe)

Range:

Function:

10000.000

Ohm

*

[0 -

10000.000

Ohm]

Enter the equivalent iron loss

resistance (R

Fe

) value to

compensate for iron loss in the

motor.

The R

Fe

value cannot be found by

performing an Auto Tune.

The R

Fe

value is especially

important in torque control

applications. If R

Fe

is unknown,

leave P-36 Iron Loss Resistance (Rfe)

on default setting.

P-37 d-axis Inductance (Ld)

Range:

Function:

0 mH

*

[0.000 -

1000.000 mH]

Enter the value of the d-axis

inductance. Obtain the value from the

permanent magnet motor data sheet.

The d-axis inductance cannot be found

by performing an Auto Tune.

P-46 Position Detection Gain

Range:

Function:

100 %

*

[20 - 200 %] Adjusts the amplitude of the test pulse

during position detection at start. Adjust

this parameter to improve the position

measurement.