E-10 Accel Time 2

Range:

Function:

the output current does not exceed the current

limit in F-43 Current Limit during ramping. The

value 0.00 corresponds to 0.01 s in speed mode.

See decel time in E-11 Decel Time 2.

Par

. E − 10 =

tacc

s

x

ns

RPM

ref

RPM

E-11 Decel Time 2

Range:

Function:

3.00

s

*

[0.01

- 3600

s]

Enter the decel time from the rated motor speed

n

s

to 0 RPM. Choose a decel time such that no

over-voltage arises in the inverter due to

regenerative operation of the motor, and such

that the generated current does not exceed the

current limit set in F-43 Current Limit. The value

0.00 corresponds to 0.01 s in speed mode. See

accel time in E-10 Accel Time 2.

Par

. E − 11 =

tdec

s

x

ns

RPM

ref

RPM

E-12 Accel Time 3

Range:

Function:

3.00 s

*

[0.01 -

3600 s]

Enter the accel time from 0 RPM to the rated

motor speed n

s

. Choose a accel time such

that the output current does not exceed the

current limit in F-43 Current Limit during

ramping. The value 0.00 corresponds to 0.01

s in speed mode. See decel time in

E-13 Decel Time 3.

E-13 Decel Time 3

Range:

Function:

3.00

s

*

[0.01

- 3600

s]

Enter the decel time from the rated motor speed

n

s

to 0 RPM. Choose a decel time such that no

over-voltage arises in the inverter due to

regenerative operation of the motor, and such

that the generated current does not exceed the

current limit set in F-43 Current Limit. The value

0.00 corresponds to 0.01 s in speed mode. See

accel time in E-12 Accel Time 3.

Par

. E − 13 =

tdec

s

x

ns

RPM

ref

RPM

E-14 Accel Time 4

Range:

Function:

3.00

s

*

[0.01 -

3600 s]

Enter the accel time from 0 RPM to the rated

motor speed n

s

. Choose a accel time such that

the output current does not exceed the current

limit in F-43 Current Limit during ramping. The

value 0.00 corresponds to 0.01 s in speed mode.

See decel time in E-15 Decel Time 4.

Par

. E − 14 =

tacc

s

x

ns

RPM

ref

RPM

E-15 Decel Time 4

Range:

Function:

3.00

s

*

[0.01

- 3600

s]

Enter the decel time from the rated motor speed

n

s

to 0 RPM. Choose a decel time such that no

over-voltage arises in the inverter due to

regenerative operation of the motor, and such

that the generated current does not exceed the

current limit set in F-43 Current Limit. The value

0.00 corresponds to 0.01 s in speed mode. See

accel time in E-14 Accel Time 4.

Par

. E − 15 =

tdec

s

x

ns

RPM

ref

RPM

3.4.3 E-2# Digital Output

Parameters to configure terminal 27 and 29 digital outputs
controlled by serial communications and to configure Relay
1 and Relay 2.

Parameters for configuring the output functions for the
output terminals. The 2 solid-state digital outputs are
common for terminals 27 and 29. Set the I/O function for
terminal 27 in E-51 Terminal 27 Mode, and set the I/O
function for terminal 29 in E-52 Terminal 29 Mode. These
parameters cannot be adjusted while the motor is running.

[0]

No operation

Default for all digital outputs and relay

outputs

[1]

Control ready

The control board receives supply

voltage.

[2]

Drive ready

The frequency converter is ready for

operation and applies a supply signal on

the control board.

[3]

Drive ready /

remote control

The frequency converter is ready for

operation and is in Auto mode.

[4]

Enable / no

warning

Ready for operation. No start or stop

command is been given (start/disable).

There are no warnings.

[5]

Drive running

Motor is running.

[6]

Running / no

warning

Output speed is higher than the speed

set in H-81 Min Speed for Function at Stop

[RPM]. The motor is running and there

are no warnings.

[7]

Run in range /

no warning

Motor is running within the programmed

current and speed ranges set in

H-70 Warning Current Low to

H-73 Warning Speed High. There are no

warnings.

[8]

Run on

reference / no

warning

Motor runs at reference speed.

[9]

Alarm

An alarm activates the output. There are

no warnings.

[10]

Alarm or

warning

An alarm or a warning activates the

output.

Parameter Descriptions

AF-650 GP Programming Guide

46

DET-618C

3