17 restoring drive to factory settings – GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 23

Advertising
background image

2.1.17 Restoring Drive to Factory Settings

The drive can be restored to factory settings in two ways.

Recommended

1.

Select H-03 Restore Factory Settings

2.

Press [OK]

3.

Select [2] Restore Factory Settings

4.

Press [OK]

5.

Cut off the mains supply and wait until the
display turns off.

6.

Reconnect the mains supply - the frequency
converter is now reset.

H-03 Restore Factory Settings restores all except:

SP-50 RFI Filter

O-30 Protocol

O-31 Address

O-32 Drive Port Baud Rate

O-35 Minimum Response Delay

O-36 Max Response Delay

O-37 Max Inter-Char Delay

ID-00 Operating hours to ID-05 Over Volt's

ID-20 Historic Log: Event to ID-22 Historic Log:
Time

ID-30 Fault Log: Error Code to ID-32 Alarm Log:
Time

Manual Restore of Factory Settings

1.

Disconnect from mains and wait until the display
turns off

2.

Press [Status] - [Main Menu] - [OK] at the same
time while power up for keypad

3.

Release the keys after 5 s.

4.

The frequency converter is now programmed
according to default settings.

Manual restores all except:

ID-00 Operating hours

ID-03 Power Up's

ID-04 Over Temp's

ID-05 Over Volt's

NOTE

A manual restore also resets serial communication, RFI
filter settings (SP-50 RFI Filter) and fault log settings.

How to Program

AF-650 GP Programming Guide

22

DET-618C

2

2

Advertising