20 b-## brakes, Dc hold current ), Dc brake current ) d – GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 129: Dc brake, Current, B-03 dc brake cut in speed [rpm, B-02 dc braking time, Dc hold current, B-00 dc hold, Dc brake current

Advertising
background image

3.20 B-##

Brakes

Parameter group related to the brake features in the drive.

3.20.1 B-0# DC Brake

Parameters to configure the DC brake and DC hold
functions.

B-00 DC Hold Current

Range:

Function:

50 %

*

[0 -

160 %]

Enter a value for holding current as a

percentage of the rated motor current I

M,N

set

in P-03 Motor Current. 100% DC holding current

corresponds to I

M,N

.

This parameter holds the motor function

(holding torque) or pre-heats the motor.

This parameter is active if DC hold is selected in

F-25 Start Function [0] or H-80 Function at Stop

[1].

NOTE

The maximum value depends on the rated motor current.
Avoid 100 % current for too long. It may damage the
motor.
Low values of DC hold will produce larger than expected
currents with larger motor power sizes. This error will
increase as the motor power increases.

B-01 DC Brake Current

Range:

Function:

50

%

*

[0 -

1000 %]

Enter a value for current as a percentage of the

rated motor current I

M,N

, see P-03 Motor Current.

100% DC braking current corresponds to I

M,N

.

DC brake current is applied on a stop

command, when the speed is lower than the

limit set in B-03 DC Brake Cut In Speed [RPM];

when the DC Brake Inverse function is active; or

via the serial communication port. The braking

current is active during the time period set in

B-02 DC Braking Time.

NOTE

The maximum value depends on the rated motor current.
Avoid 100 % current for too long. It may damage the
motor.

B-02 DC Braking Time

Range:

Function:

10 s

*

[0 - 60 s] Set the duration of the DC braking current set

in B-01 DC Brake Current, once activated.

B-03 DC Brake Cut In Speed [RPM]

Range:

Function:

0 RPM

*

[0 - 60000

RPM]

Set the DC brake cut-in speed for

activation of the DC braking current

set in B-01 DC Brake Current, upon a

stop command.

B-04 DC Brake Cut In Speed [Hz]

Range:

Function:

0.0 Hz

*

[0 - 1000.0 Hz] Set the DC brake cut-in speed for

activation of the DC braking current set

in B-01 DC Brake Current, upon a stop

command.

B-05 Maximum Reference

Range:

Function:

par. F-53 ReferenceFeed-

backUnit

*

[par. F-52 - 999999.999

ReferenceFeedbackUnit]

B-06 Parking Current

Range:

Function:

50 %

*

[0 - 1000 %] Set current as percentage of rated motor

current, P-03 Motor Current. Will be used

when enabled in F-20 PM Start Mode.

B-07 Parking Time

Range:

Function:

3 s

*

[0.1 - 60 s] Set the duration of the Parking Current set in

B-06 Parking Current, once activated.

3.20.2 B-1# Brake Energy Funct.

Parameters to configure the dynamic braking functions in
the drive. Note! This applies only to drives ordered with
the optional factory installed brake chopper option.

B-10 Brake Function

Option:

Function:

[0]

*

Off

No brake resistor is installed.

[1]

Resistor

brake

A brake resistor is incorporated in the system,

for dissipation of surplus brake energy as heat.

Connecting a brake resistor allows a higher DC

link voltage during braking (generating

operation). The Resistor brake function is only

active in frequency converters with an integral

dynamic brake.

[2]

AC brake

Is selected to improve braking without using a

brake resistor. This parameter controls an

overmagnetization of the motor when running

with a generatoric load. This function can

improve the OVC-function. Increasing the

electrical losses in the motor allows the OVC

function to increase the braking torque without

exceeding the over voltage limit. Please note

Parameter Descriptions

AF-650 GP Programming Guide

128

DET-618C