PI-51 Process PID Feed Fwd Gain

Range:

Function:

1

*

[0 -

100]

The feed forward is used to obtain the desired

level, based on a well-known signal available. The

PID controller then only takes care of the smaler

part of the control, necessary because of unknown

characters. The standard feed fwd factor in

PI-38 Process PID Feed Forward Factor is always

related to the reference whereas PI-51 Process PID

Feed Fwd Gain has more choices. In winder

applications, the feed fwd factor will typically be

the line speed of the system.

PI-52 Process PID Feed Fwd Ramp up

Range:

Function:

0.01 s

*

[0.01 - 10 s] Controls the dynamics of the feed forward

signal when ramping up.

PI-53 Process PID Feed Fwd Ramp down

Range:

Function:

0.01 s

*

[0.01 - 10 s] Controls the dynamics of the feed forward

signal when ramping down.

PI-56 Process PID Ref. Filter Time

Range:

Function:

0.001 s

*

[0.001 - 1 s] Set a time constant for the reference first

order low-pass filter. The low-pass filter

improves steady-state performance and

dampens oscillations on the reference/

feedback signals. However severe filtering

can be detrimental to dynamic

performance.

PI-57 Process PID Fb. Filter Time

Range:

Function:

0.001 s

*

[0.001 - 1 s] Set a time constant for the feedback first

order low-pass filter. The low-pass filter

improves steady-state performance and

dampens oscillations on the reference/

feedback signals. However severe filtering

can be detrimental to dynamic

performance.

PI-60 Process PID Error

Range:

Function:

0 %

*

[-200 - 200 %]

PI-61 Process PID Output

Range:

Function:

0 %

*

[-200 - 200 %]

PI-62 Process PID Clamped Output

Range:

Function:

0 %

*

[-200 - 200 %]

PI-63 Process PID Gain Scaled Output

Range:

Function:

0 %

*

[-200 - 200 %]