H-73 warning speed high, H-72 warning speed low, H-76 warning feedback low – GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 69: H-77 warning feedback high, 7 h-8# stop adjustments

Advertising
background image

H-72 Warning Speed Low

Range:

Function:

0 RPM

*

[0 - par.

H-73 RPM]

Enter the n

LOW

value. When the motor

speed exceeds this limit, the display reads

Speed Low. The signal outputs can be

programmed to produce a status signal on

terminal 27 or 29 and on relay output 01

or 02.

H-73 Warning Speed High

Range:

Function:

par.

F-17

RPM

*

[par.

H-72 -

par. F-17

RPM]

Enter the n

HIGH

value. When the motor

speed exceeds this limit, the display reads

Speed High. The signal outputs can be

programmed to produce a status signal on

terminal 27 or 29 and on relay output 01 or

02. Program the upper signal limit of the

motor speed, n

HIGH

, within the normal

working range of the frequency converter.

Refer to Illustration 3.31.

H-74 Warning Reference Low

Range:

Function:

-999999.999

*

[-999999.999 -

par. H-75]

Enter the lower reference limit.

When the actual reference falls

below this limit, the display

indicates Ref

LOW

. The signal

outputs can be programmed to

produce a status signal on

terminal 27 or 29 and on relay

output 01 or 02.

H-75 Warning Reference High

Range:

Function:

999999.999

*

[par. H-74 -

999999.999]

Enter the upper reference limit.

When the actual reference

exceeds this limit, the display

reads Ref High. The signal outputs

can be programmed to produce a

status signal on terminal 27 or 29

and on relay output 01 or 02.

H-76 Warning Feedback Low

Range:

Function:

-999999.999

ReferenceFeed-

backUnit

*

[-999999.999 -

par. H-77

ReferenceFeed-

backUnit]

Enter the lower

feedback limit. When the

feedback falls below this

limit, the display reads

Feedb Low. The signal

outputs can be

programmed to produce

a status signal on

terminal 27 or 29 and

on relay output 01 or

02.

H-77 Warning Feedback High

Range:

Function:

999999.999

ReferenceFeed-

backUnit

*

[par. H-76 -

999999.999

ReferenceFeed-

backUnit]

Enter the upper

feedback limit. When

the feedback exceeds

this limit, the display

reads Feedb High. The

signal outputs can be

programmed to produce

a status signal on

terminal 27 or 29 and

on relay output 01 or

02.

H-78 Missing Motor Phase Function

Option:

Function:

Displays an alarm in the event of a

missing motor phase.

[0]

*

Disabled

No alarm is displayed if a missing

motor phase occurs.

[1]

Trip 100 ms

An alarm is displayed if a missing

motor phase occurs.

[2]

Trip 1000 ms

[3]

Trip 100 ms lim 3

phase detec.

[5]

Motor Check

NOTE

This parameter cannot be adjusted while the motor is
running.

3.7.7 H-8# Stop Adjustments

Parameters to configure the special stop features for the
motor and Load Type and Min/Max Inertia.

H-80 Function at Stop

Option:

Function:

Select the frequency converter function

after a stop command or after the speed is

deceled to the settings in H-81 Min Speed

for Function at Stop [RPM].

[0]

*

Coast

Leaves motor in free mode. The motor is

disconnected from the frequency converter.

[1]

DC hold

Energizes motor with a DC holding current

(see B-00 DC Hold Current).

[2]

Motor check

Checks if a motor has been connected.

[3]

Pre-

magnetizing

Builds up a magnetic field while the motor

is stopped. This allows the motor to

produce torque quickly at subsequent start

commands (asynchronous motors only). This

Pre-magnetizing function does not help the

very first start command. Two different

Parameter Descriptions

AF-650 GP Programming Guide

68

DET-618C

3