14 value, step-by-step, 15 read-out and programming of indexed parameters, 16 local control keys – GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 22

Advertising
background image

2.1.13 Infinitely Variable Change of

Numeric Data Value

If the chosen parameter represents a numeric data value,

select a digit with [

] [

].

Illustration 2.19 Selecting a Digit

Change the selected digit infinitely variably with [

] [

].

The chosen digit is indicated by the cursor. Place the
cursor on the digit to save and press [OK].

2.1.14 Value, Step-by-Step

Certain parameters can be changed step by step or
infinitely varying. This applies to P-07 Motor Power [kW],
F-05 Motor Rated Voltage and F-04 Base Frequency.
The parameters are changed both as a group of numeric
data values and as numeric data values infinitely varying.

2.1.15 Read-out and Programming of

Indexed Parameters

Parameters are indexed when placed in a rolling stack.
ID-30 Fault Log: Error Code to ID-32 Alarm Log: Time contain
a fault log which can be read out. Choose a parameter,

press [OK], and use [

] [

] to scroll through the value log.

Use C-05 Multi-step Frequency 1 - 8 as another example:

Choose the parameter, press [OK], and use [

] [

] to scroll

through the indexed values. To change the parameter
value, select the indexed value and press [OK]. Change the

value by pressing [

] [

]. Press [OK] to accept the new

setting. Press [Cancel] to abort. Press [Back] to leave the
parameter.

2.1.16 Local Control Keys

Keys for local control are found at the bottom of the
keypad.

Illustration 2.20 Keypad Keys

[Hand]
enables control of the frequency converter via the keypad.
[Hand] also starts the motor and it is now possible to enter
the motor speed data by means of the arrow keys. The key
can be selected as [1] Enable or [0] Disable via K-40 [Hand]
Button on Keypad
.
External stop signals activated by means of control signals
or a serial bus will override a 'start' command via the
keypad.
The following control signals are still active when [Hand] is
activated:

[Hand] - [Off] - [Auto]

Reset

Coasting stop inverse

Reversing

Set-up select lsb - Set-up select msb

Stop command from serial communication

Quick stop

DC brake

[Off]
stops the connected motor. The key can be selected as [1]
Enable
or [0] Disable via K-41 [Off] Button on Keypad.
If no external stop function is selected and the [Off] key is
inactive the motor can be stopped by disconnecting the
voltage.

[Auto]
enables the frequency converter to be controlled via the
control terminals and/or serial communication. When a
start signal is applied on the control terminals and/or the
bus, the frequency converter will start. The key can be
selected as [1] Enable or [0] Disable via K-42 [Auto] Button
on Keypad
.

NOTE

An active HAND-OFF-AUTO signal via the digital inputs has
higher priority than the control keys [Hand] [Auto].

[Reset]
is used for resetting the frequency converter after an alarm
(trip). It can be selected as [1] Enable or [0] Disable via
K-43 [Reset] Button on Keypad.

How to Program

AF-650 GP Programming Guide

DET-618C

21

2

2