F-08 Decel Time 1

Range:

Function:

corresponds to 0.01 s in speed mode. See accel

time in F-07 Accel Time 1.

Par

.

F

− 08 =

tdec

s

x

ns

RPM

ref

RPM

F-09 Torque Boost

Range:

Function:

100 %

*

[0 - 300

%]

Enter the % value to compensate voltage in

relation to load when the motor is running at

low speed and obtain the optimum U/f

characteristic. The motor size determines the

frequency range within which this parameter

is active.

Motor size

Change over

0.25 kW-7.5 kW

<10 Hz

Illustration 3.5 Changeover

3.3.2 F-1# Fundamental 1

Parameters to configure drive electronic overload and
high/low speed limits.

F-10 Electronic Overload

Option:

Function:

Thermal motor protection can be

implemented using a range of techniques:

Via a PTC sensor in the motor

windings connected to one of the

analog or digital inputs (F-12 Motor

Thermistor Input). See 3.3.3.1 PTC

Thermistor Connection.

Via a KTY sensor in the motor

winding connected to an analog

F-10 Electronic Overload

Option:

Function:

input (H-96 KTY Thermistor Input).

See 3.3.3.2 KTY Sensor Connection.

Via calculation of the thermal load,

based on the actual load and time.

The calculated thermal load is

compared with the rated motor

current I

M,N

and the rated motor

frequency f

M,N

. See 3.3.3.3 Electronic

Thermal Overload.

Via a mechanical thermal switch

(Klixon type). See 3.3.3.4 Klixon.

For the North American market: The

electronic overload functions provide class

20 motor overload protection in accordance

with NEC.

[0]

*

No

protection

Continuously overloaded motor, when no

warning or trip of the frequency converter is

required.

[1]

Thermistor

warning

Activates a warning when the connected

thermistor or KTY-sensor in the motor reacts

in the event of motor over-temperature.

[2]

Thermistor

trip

Stops (trips) frequency converter when

connected thermistor or KTY sensor in the

motor reacts in the event of motor over-

temperature.

The thermistor cut-out value must be > 3

k

Ω.

Integrate a thermistor (PTC sensor) in the

motor for winding protection.

[3]

Elec. OL

Warning 1

Calculates the load when set-up 1 is active

and activates a warning on the display when

the motor is overloaded. Program a warning

signal via one of the digital outputs.

[4]

Elec. OL Trip

1

Calculates the load when set-up 1 is active

and stops (trips) frequency converter when

the motor is overloaded. Program a warning

signal via one of the digital outputs. The

signal appears in the event of a warning

and if the frequency converter trips (thermal

warning).

[5]

Elec. OL

Warning 2

[6]

Elec. OL Trip

2

[7]

Elec. OL

Warning 3

[8]

Elec. OL Trip

3

[9]

Elec. OL

Warning 4

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

33