3.19 LC-## Logic Controller

Parameter group related to programming the drive's built-
in Logic Controller. The Logic Controller consists of a series
of user defined actions (see LC-52 Logic Controller Action)
that are executed when the corresponding user-defined
events are met.

3.19.1 LC-0# LC Settings

Parameters to configure the activation, deactivations and
reset of the Logic Controller (LC).

LC-00 Logic Controller Mode

Option:

Function:

[0]

*

Off

Disables the Logic Controller.

[1]

On

Enables the Logic Controller.

LC-01 Start Event

Select the boolean (TRUE or FALSE) input to activate Logic

Controller.

Option:

Function:

[0]

*

False

Select the boolean (TRUE or FALSE)

input to activate Logic Controller.

Enters the fixed value - FALSE

[1]

True

Enters the fixed value - TRUE.

[2]

Running

The motor is running.

[3]

In range

The motor is running within the

programmed current and speed

ranges set in H-70 Warning Current

Low to H-73 Warning Speed High.

[4]

On reference

The motor is running on reference.

[5]

Torque limit

The torque limit, set in F-40 Torque

Limiter (Driving) or F-41 Torque Limiter

(Braking), has been exceeded.

[6]

Current Limit

The motor current limit, set in

F-43 Current Limit, has been

exceeded.

[7]

Out of current

range

The motor current is outside the

range set in F-43 Current Limit.

[8]

Below I low

The motor current is lower than set

in H-70 Warning Current Low.

[9]

Above I high

The motor current is higher than set

in H-71 Warning Current High.

[10]

Out of speed range The speed is outside the range set in

H-72 Warning Speed Low and

H-73 Warning Speed High.

[11]

Below speed low

The output speed is lower than the

setting in H-72 Warning Speed Low.

[12]

Above speed high

The output speed is higher than the

setting in H-73 Warning Speed High.

LC-01 Start Event

Select the boolean (TRUE or FALSE) input to activate Logic

Controller.

Option:

Function:

[13]

Out of feedb. range The feedback is outside the range set

in H-76 Warning Feedback Low and

H-77 Warning Feedback High.

[14]

Below feedb. low

The feedback is below the limit set in

H-76 Warning Feedback Low.

[15]

Above feedb. high

The feedback is above the limit set in

H-77 Warning Feedback High.

[16]

Thermal warning

The thermal warning turns on when

the temperature exceeds the limit in

the motor, the frequency converter,

the brake resistor or the thermistor.

[17]

Line voltage out of

range

The mains voltage is outside the

specified voltage range.

[18]

Reversing

The output is high when the

frequency converter is running

counter clockwise (the logical product

of the status bits “running” AND

“reverse”).

[19]

Warning

A warning is active.

[20]

Alarm (trip)

A (trip) alarm is active.

[21]

Alarm (trip lock)

A (Trip lock) alarm is active.

[22]

Comparator 0

Use the result of comparator 0.

[23]

Comparator 1

Use the result of comparator 1.

[24]

Comparator 2

Use the result of comparator 2.

[25]

Comparator 3

Use the result of comparator 3.

[26]

Logic rule 0

Use the result of logic rule 0.

[27]

Logic rule 1

Use the result of logic rule 1.

[28]

Logic rule 2

Use the result of logic rule 2.

[29]

Logic rule 3

Use the result of logic rule 3.

[33]

Digital input DI18

Use the result of digital input 18.

[34]

Digital input DI19

Use the result of digital input 19.

[35]

Digital input DI27

Use the result of digital input 27.

[36]

Digital input DI29

Use the result of digital input 29.

[37]

Digital input DI32

Use the result of digital input 32.

[38]

Digital input DI33

Use the result of digital input 33.

[39]

Start command

A start command is issued.

[40]

Drive stopped

A stop command (Jog, Stop, Qstop,

Coast) is issued – and not from the

Logic Controller itself.

[41]

Reset Trip

A reset is issued

[42]

Auto-reset Trip

An Auto reset is performed.

[43]

Ok key

[OK] is pressed.

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

119