Lenze EVF9383 User Manual

Page 103

Advertising
background image

Control terminals

With function "Safe torque off" active

5.6

5.6.3

l

5.6−5

EDSVF9383V EN 7.1−04/2012

ƒ If a freely assignable digital output (e.g. X5/A1) is assigned

permanently to HIGH level, it serves as an internal voltage source. Every
output has a maximum load capacity of 50 mA.
– The relay K

SR

and two digital inputs (X5/28 and e.g. X5/E1) can be

supplied with voltage via a digital output.

– Two digital outputs must be connected in parallel and assigned

permanently to HIGH level in order to obtain the maximum wiring
(relays K

SR

and X5/E1 ... X5/E5, X5/ST1).

ƒ For the supply of the analog inputs (X6/1, X6/2 and X6/3, X6/4) you

have to set a freely assignable analog output (e. g. X6/63) permanently
to HIGH level.

GND2

+24V

+5 V

DIGOUT4

E5

A2 A3 A4 ST1ST2 59

39

3k

47k

50mA

50mA

50mA

50mA

X5 28 E1 E2 E3 E4

3k

3k

3k

3k

3k

X11 K31K32 33 34

S1

S2

IN1 IN2 IN3 IN4

+

K

SR

A1

Z1

X3

GND1

GND1

X6

1

2

3

4

7

7

62 63

242R

1
2
3
4
5
6

100k

100k

100k

100k

3.3nF

AIN1

AIN2

AOUTx

AOUT2

AOUT1

1

3

2

4

7

10k

10k

9300vec135

Fig. 5.6−3

Wiring of digital and analog inputs/outputs with active "Safe torque off" function
and internal voltage source

S1

Deactivate pulse inhibit (1st disconnecting path)

S2

Enable controller (2nd disconnecting path)

Z1

Programmable logic controller (PLC)
The PLC monitors the ˜Safe torque off˜ function

X5/A4 Feedback via a digital output (e. g. DIGOUT4)

NO contact or NC contact

Z

Load
Minimum wiring required for operation

Terminal assignment in the Lenze setting:

^ 5.6−9

)

Note!

If you load a basic configuration C0005 = xx1x (e.g. 1010 for
speed control with control via terminals), the following terminals
are switched to a fixed signal level:

ƒ

Terminal X5/A1 to FIXED1 (corresponds to DC 24 V).

ƒ

Terminal X6/63 to FIXED100% (corresponds to 10 V).

Supply via internal voltage
source