Selection of the correct operating mode 6.2 – Lenze EVF9383 User Manual

Page 124

Advertising
background image

Selection of the correct operating mode

6.2

l

6.2−2

EDSVF9383V EN 7.1−04/2012

The frequency inverter is mainly designed for the applications listed in the
below table.

The table helps you to select the correct operating mode for your application:

ƒ C0006 = 5: V/f characteristic control with constant V

min

boost

ƒ C0006 = 1: Vector control

Power range 110 ... 400 kW

Selection of the operating mode in C0006

Motor cable

shielded

£

100 m

unshielded

£

200 m

Motor cable

shielded

>

100 m

unshielded

>

200 m

Applications with asynchronous motors

recommen

ded

alternativ

ely

recommen

ded

alternativ

ely

Single drives

Drives with constant load

5

1

5

Drives with heavy start conditions

1

5

5

Travelling drives, conveyor belts

5

1

5

Pump drives, fan drives

1)

5

5

Extruder drives

5

1

5

Drives for wire drawing machines

5

1

5

Drives for rolling machines

5

1

5

Drives for rewinders with dancer
(speed−controlled)

1

5

Group drives
(the resulting motor cable length is decisive
I

res

)

5

5

l

res

+ (i

Ǹ

@ (l

1

) l

2

) AAA ) l

i

))

1)

A square voltage characteristic (C0014 = 1) is recommended for this application