4 free configuration of analog outputs, Free configuration of analog outputs – Lenze EVF9383 User Manual

Page 140

Advertising
background image

Changing the assignment of the control terminals X5 and X6
Free configuration of analog outputs

6.5
6.5.4

l

6.5−6

EDSVF9383V EN 7.1−04/2012

6.5.4

Free configuration of analog outputs

ƒ The analog outputs (X6/62, X6/63) can be freely linked with internal

analog process or monitoring signals. The controller outputs a voltage
proportional to the internal signal at the analog outputs.

ƒ One signal source can be linked with several targets.

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0108

−199.99

{0.01 %}

199.99 Free control code FCODE108/1

and FCODE108/2

^
6.5−6

See System
Manual
(extension)

1 FCODE (gain)

100.0

0

Gain of analog output signal
AOUT1 (X6/62)

l

100 % = gain 1

2 FCODE (gain)

100.0

0

Gain of analog output signal
AOUT2 (X6/63)

l

100 % = gain 1

C0109

−199.99

{0.01 %}

199.99 Free control code FCODE109/1

and FCODE109/2

1 FCODE (offset)

0.00

Offset of analog output signal
AOUT1 (X6/62)

2 FCODE (offset)

0.00

Offset of analog output signal
AOUT2 (X6/63)

Analog outputs can be linked with internal analog signals by entering the
selection figure of the internal signal into the code of C0431 (AOUT1, X6/62)
or C0436 (AOUT2, X6/63).

Example

ƒ C0436 = 5006

ð signal source for X6/63 is the actual motor voltage

I

Tip!

ƒ

A list with all selection figures is included in the chapter
"Configuration"

® "Selection lists".

ƒ

For signal linkage we recommend the function block editor in
GDC (ESP−GDC2).

Set gain (C0108) and offset (C0109) to adapt the output signal to the
application.

With an internal signal of 100 % and a gain of 1, a voltage of 10 V is output
at the terminal.

Description

Linking signals

Adjustment