Lenze EVF9383 User Manual

Page 151

Advertising
background image

Adjusting the motor

Motor temperature monitoring with KTY

6.6

6.6.4

l

6.6−11

EDSVF9383V EN 7.1−04/2012

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0594 MONIT SD6

3

0

TRIP

Activation of the motor
temperature monitoring with KTY
at X8

l

Use C0594 = 0 or 2 to activate
monitoring

l

In case of a short circuit or
interruption at X8/5 and X8/8
the fault message SD6 is
activated

l

Configuration of the response
when exceeding the motor
temperature
– Fixed operating temperature

in C0583

– Variable operating

temperature in C0584

^
6.6−10

See System
Manual
(extension)

2

Warning

3

Off

C1190 Motor PTC

selection

0

Temperature characteristic for PTC
thermistors

l

Selection of the characteristic
for PTC thermistors at X7 or X8
for detecting the motor
temperature

^
6.6−10

0

Standard

Characteristic for PTC thermistors
in Lenze motors

1

Characteristic

Characteristic for
application−specific PTC
thermistors

C1191 Temperature

characteristic

0

{1 °C}

255 Temperature range for PTC

thermistors

l

Define temperature points on
the characteristic for PTC
thermistors

1 Temperature 1

100

Temperature point 1

2 Temperature 2

150

Temperature point 2

C1192 Resistance

characteristic

0

{1

W}

3000 Resistance characteristic for PTC

thermistors

l

Define resistance points on the
characteristic for PTC
thermistors

1 Resistance 1

1670

Resistance point 1

2 Resistance 2

2225

Resistance point 2

Advertising