Basic devices in the power range 110 ... 200 kW

Motor connection

5.4

5.4.7

l

5.4−7

EDSVF9383V EN 7.1−04/2012

5.4.7

Motor connection

ƒ To comply with the EMC regulations, Lenze recommends to use

shielded motor cables.

ƒ Shield clamps are not included in the scope of supply.

(

Stop!

The user is responsible for sufficient strain relief!

BR2

BR1

PE

U

V

W

40 mm

PE

15-20 Nm

M6

133-176 lb-in

U, V, W

25-30 Nm

M8

221-264 lb-in

0

max.

300 mm

1

9300VEC005

Fig. 5.4−6

Motor connection example

BR1, BR2 Brake resistors can only be operated with variants V060, V110, V270

and V300

0

Connect the motor cable shield with a surface as large as possible to
the control cabinet mounting plate by using the clamps.

1

Conductive surface

Ensure to have the poles right!
Do not exceed the maximum motor cable length!

9300 vector

Installation in accordance with EN 60204−1

U, V, W

PE

Type

[mm

2

]

[mm

2

]

EVF9335−EV
EVF9335−EVVxxx

150

2 × 50

1)

95

EVF9336−EV
EVF9336−EVVxxx

150

2 × 50

1)

95

EVF9337−EV
EVF9337−EVVxxx

150

2 × 50

1)

95

EVF9338−EV
EVF9338−EVVxxx

240

2 × 95

1)

150

1)

Two conductors per path; both conductors must have the same
cross−section

Observe the national and regional legislation

Cable cross−section