Lenze EVF9383 User Manual

Page 94

Advertising
background image

Basic devices in the power range 250 ... 400 kW
Motor connection

5.5
5.5.8

l

5.5−12

EDSVF9383V EN 7.1−04/2012

0

1

BR2

BR2

BR1

BR1

PE

PE

U

U

V

V

W

W

40 mm

40 mm

PE

15-20 Nm

M6

133-176 lb-in

PE

15-20 Nm

M6

133-176 lb-in

U, V, W

25-30 Nm

M8

221-264 lb-in

U, V, W

25-30 Nm

M8

221-264 lb-in

2

2

3

3

max.

300 mm

max.

300 mm

9300VEC036

Fig. 5.5−12

Motor connection example

BR1, BR2 Brake resistors can only be operated with variants V060, V110, V270

and V300

0

Master terminals

1

Slave terminals

2

Connect the motor cable shield with a surface as large as possible to
the control cabinet mounting plate by using the clamps.

3

Conductive surface

Ensure to have the poles right!
Do not exceed the maximum motor cable length!

9300 vector

Installation in accordance with EN 60204−1

U, V, W

PE

Type

[mm

2

]

[mm

2

]

Master

Slave

Master

Slave

EVF9381−EV
EVF9381−EVVxxx

150

2 Ч 50

1)

150

2 Ч 50

1)

95

95

EVF9382−EV
EVF9382−EVVxxx

150

2 Ч 50

1)

150

2 Ч 50

1)

95

95

EVF9383−EV
EVF9383−EVVxxx

240

2 Ч 95

1)

240

2 Ч 95

1)

150

150

1)

Two conductors per path; both conductors must have the same
cross−section

Observe the national and regional legislation

Motor connection

Cable cross−section