Lenze EVF9383 User Manual

Page 153

Advertising
background image

Adjusting the motor

Motor temperature monitoring with KTY

6.6

6.6.4

l

6.6−13

EDSVF9383V EN 7.1−04/2012

The temperature and resistance range can be adapted to the KTY used.

ƒ C1190 = 0: Fixed operating range for KTY in Lenze motors (Lenze

setting)

ƒ C1190 = 1: Adjustable operating range

T [ ° C ]

R [ O h m ]

R 2

( C 1 1 9 2 / 2 )

T 1

( C 1 1 9 1 / 1 )

R 1

( C 1 1 9 2 / 1 )

T 2

( C 1 1 9 1 / 2 )

a

Fig. 6.6−3

Setting of the operating range for the KTY (C1190 = 1)

The operating range is specified by means of limit values and is in the almost
linear section of the graph (a). The operating values are determined by
interpolation.
C1191/1
C1191/2

Setting of the lower and upper temperature value (T1, T2)
corresponding to the KTY used.

C1192/1
C1192/2

Setting of the lower and upper resistance value corresponding to
the KTY used.

Adjustment of KTY operating
range